In order to comply with CSA C22.2 No. 14-2010 (cUL) following external Filters and Mains
Chokes manufactured by Karl E. Brinkmann need to be installed:
Voltage class 400/480 V
Talla de la unidad
28
29
30
31
32
33
34
35
36
37
38
Detailed wiring Instructions for the external Filters and Mains Chokes
as specified in ILL.No. 19 shall be present in the Installation Instructions of the products.
Short Circuit rating and Branch Circuit Protection:
Following marking shall be provided:
All 480V Models:
„Suitable For Use On A Circuit Capable Of Delivering Not More Than 100 kA rms Symmetrical
Amperes, 480 Volts Maximum when Protected by Class J or RK5 Fuses, rated ___ Amperes
as specified in table I":
or when Protected by A Circuit Breaker Having an Interrupting rating Not Less than 100 kA
rms Symmetrical Amperes, 480V maximum, rated ___ Amperes as specified in table I":
Table I Branch Circuit Protection of inverter series F5 / F6 – P – housing:
*a) Class J or RK5 as specified below:
Variador F5/F6
28
29
30
31
32
1x28E4T60-1001
1x30E4T60-1001
1x30E4T60-1001
2x28E4T60-1001
2x28E4T60-1001
2x28E4T60-1001
2x30E4T60-1001
2x30E4T60-1001
3x28E4T60-1001
3x30E4T60-1001
3x30E4T60-1001
Tensión de entrada [ V ]
480 / 3ph
480 / 3ph
480 / 3ph
480 / 3ph
480 / 3ph
Filtro
UL 248 Fuse type J or RK5 [A]
Anexo
Inductancia de entrada
1x28Z1B04-1000
1x29Z1B04-1000
1x30Z1B04-1000
2x28Z1B04-1000
2x28Z1B04-1000
2x28Z1B04-1000
2x29Z1B04-1000
2x30Z1B04-1000
3x28Z1B04-1000
3x29Z1B04-1000
3x30Z1B04-1000
3x400
3x500
3x600
2 x 3x400
2 x 3x400
E - 39