7. BALANCING THE UNIT
7.1 W
N
B
HAT YOU
EED TO
• A magnehelic gauge capable of measuring 0 to 1 inch of water and 2 plastic tubes.
• The balancing chart of the unit.
7.2 P
S
RELIMINARY
TAGES TO
• Seal all the unit ductwork with tape. Close all windows and doors.
• Turn off all exhaust devices such as range hood, dryer and bathroom fans.
• Make sure the balancing dampers are fully open by setting both damper balancing tools completely vertical.
• Make sure all filters are clean (if it is not the first time the unit is balanced).
7.3 B
P
ALANCING
ROCEDURE
1. Set the unit to high speed.
NOTE: Make sure that the furnace/air handler blower is ON if the installation is in any way connected to the ductwork of the cold
air return. If not, leave furnace/air handler blower OFF. If the outside temperature is below 32°F, make sure the unit is not
running in defrost while balancing. (By waiting 10 minutes after plugging the unit in, you are assured that the unit is not in a
defrost cycle.)
2. Place the magnehelic gauge on a level surface and adjust it to zero.
3. Connect tubing from gauge to EXHAUST air flow pressure taps (the ones
with arrows, see insets in illustration at right).
Be sure to connect the tubes to their appropriate high/low fittings. If the
gauge drops below zero, reverse the tubing connections.
4. Note the CFM value from balancing chart on unit.
5. Repeat steps 3 and 4, but to FRESH air flow pressure taps.
6. Match highest CFM value to lowest by adjusting the balancing damper
corresponding to the highest value.
See example below:
F
F
LOW
CFM
IN
120
125
130
135
140
145
150
In that case, there is 150 CFM in FRESH air and 125 CFM in EXHAUST air. Then, adjust (close) the FRESH air balancing damper
until the FRESH air flow matchs the EXHAUST air flow: 125 CFM (0.67 in. w.g.) with magnehelic gauge connected to FRESH air
flow pressure taps).
7. Secure both dampers in place with a fastening screw (included).
8. Write the required air flow information on a label and affix it near the unit for future reference (date, maximum speed air flows, your
name, phone number and business address).
NOTES: 1. Use conversion chart provided with the unit to convert magnehelic gauge readings to equivalent cfm values.
2. The unit is considered balanced even if there is a difference of ±10 cfm (or ± 5 l/s) between the two air flows.
U
ALANCE THE
NIT
B
U
ALANCE THE
NIT
E
RESH
XHAUST
.
.
.
.
.
.
W
G
IN
W
G
0.71
0.73
0.67
0.70
0.63
0.67
0.59
0.64
0.55
0.61
0.51
0.58
0.47
0.55
VP0017
E
XHAUST READING VALUES
F
RESH READING VALUES
18
VP0009
D
BALANCING TOOL
VR0029
S
TALE AIR FLOW
F
RESH AIR FLOW
F
ASTENING SCREW
VR0030
AMPER

Publicidad

Capítulos

Tabla de contenido
loading

Este manual también es adecuado para:

Hrv160 ecmHrv160

Tabla de contenido