9. TROUBLESHOOTING (
Table 8 B only applies for ERV140 ECM and HRV160 ECM units.
When these units have a RED flashing LED, follow these few steps before proceeding to troubleshooting:
•
Unplug the unit.
•
Unplug the green control terminal connector.
•
Remove the unit door in order to see the motors, making sure that there is no risk of injury.
•
Plug unit back and wait until the booting sequence is completed.
•
Press the integrated control push-button, and observe the LED and motors.
•
Proceed to troubleshooting.
P
ROBLEMS
The LED flashes RED as
soon as the unit is set to
low speed.
The exhaust motor does
not run at all (not even
a pulse when hitting the
button) and LED flashes
RED after 20 seconds.
The exhaust motor is
running at a wrong speed
and LED flashes RED after
20 seconds.
8 B
The supply motor does
not run at all (not even
a pulse when hitting the
button) and LED flashes
RED after 20 seconds.
The
supply
motor
running at a wrong speed
and LED flashes RED after
20 seconds.
If the problem is still not solved, reach our Technical Support:
'
)
CONT
D
P
OSSIBLE CAUSES
• The
J11
connector
misconnected or there may be a bad
contact.
• The
J5
connector
misconnected.
• The
JU1
jumper
mispositioned.
• The PCB may be defective.
• The motor may be defective.
• The
J17
connector
misconnected.
• The
JU1
jumper
mispositioned.
• The PCB may be defective.
• The motor may be defective.
• The
J4
connector
misconnected or there may be a bad
contact.
• The
JU1
jumper
mispositioned.
• The PCB may be defective.
• The motor may be defective.
is
• The
J15
connector
misconnected.
• The
JU1
jumper
mispositioned.
• The PCB may be defective.
• The motor may be defective.
Broan-NuTone LLC
Telephone: 1-800-543-3055
Y
OU SOULD TRY THIS
may
be
• Check J11 wires connection.
may
be
• Check J5 wires connection.
may
be
• Check that JU1 jumper is positioned in H (pins 1-2).
• Invert J4 and J5 connectors. If the issue is now with the
supply motor, replace PCB. If the issue remains with the
exhaust motor, replace motor.
• Replace exhaust motor.
may
be
• Check J17 wires connection.
may
be
• Check that JU1 jumper is positioned in H (pins 1-2).
• Invert J17 and J15 connectors. If the issue is now with the
supply motor, replace PCB. If the issue remains with the
exhaust motor, replace motor.
• Replace exhaust motor.
may
be
• Check J4 wires connection.
may
be
• Check that JU1 jumper is positioned in H (pins 1-2).
• Invert J4 and J5 connectors. If the issue is now with the
exhaust motor, replace PCB. If the issue remains with the
supply motor, replace motor.
• Replace supply motor.
may
be
• Check J15 wires connection.
may
be
• Check that JU1 jumper is positioned in H (pins 1-2).
• Invert J17 and J15 connectors. If the issue is now with the
exhaust motor, replace PCB. If the issue remains with the
supply motor, replace motor.
• Replace supply motor.