Wiring (continued)
Follow this diagram if using DR65A3000
with either a Prestige or TH8321R1001
RedLINK VisionPro & EIM.

Checkout

Apply power to DR65A3000. Turn the humidity control to a low RH% level to initiate a dehumidification call.
Confirm that the DR65A3000 compressor and fan turn on. The furnace blower will also turn on to circulate
air. This will take up to two minutes. Be sure to turn the control to the desired RH% or to Off when checkout
is complete. Turning the humidity control to Off will turn the DR65A3000 off.
10
EIM
U 3
U 3
U 2
U 2
1
2
U 1
U 1
DHUM R FAN C
FLOAT
3
1
IN THIS DIAGRAM, U1 CONTROLS THE DR65A FOR DEHUM AND U2
CONTROLS THE DR65A FOR VENTILATION.
2
INSTALL A JUMPER ON EIM AS SHOWN ONLY WHEN USING THE DR65
FOR VENTILATION IN ADDITION TO DEHUMIDIFICATION.
3
IF A FLOAT SWITCH IS NOT USED, THEN JUMPER THE FLOAT TERMINALS.
DR65A3000 Dehumidification System 33-00297EFS—09
Gt Rf Gf
DEHUMIDIFIER
M38419