iLumin Plus
Connecting the Supply
The suggested entry point for the supply wiring is via
the rightmost knockout on the top panel of the chassis.
This provides immediate access to the circuit breaker that
supplies the modules with power. Use a suitable conduit
and coupler to feed the source wiring safely into the
chassis.
See the diagram below for connection details. The main
earth terminal is located near to the neutral lug. The earth
connection is bonded to the main backplane of the chassis
and the outer panels.
Please consult the image below for details about the
maximum permissible supply wire gauges for the various
controller models.
Connecting Relay Loads
The relay modules (SCMR1220-NA) will be pre-mounted
on the interior DIN rail per the order specifications. Unless
otherwise specified, latching relays (single pole) will be
provided for connection to lighting loads.
Prior to relay connection, test the load directly connected to
the branch circuit breaker to verify that there are no shorts.
Remove all wire cuttings from the enclosure.
Relays are numbered 1-12 on each SCMR1220-NA module.
Using the iLumin Plus programming software each relay can
be programmed to meet control requirements. The table
below indicates the minimum wires size to be used with
various load currents.
Minimum AWG
10
12
14
Use 75C wire insulation minimum. Use copper conductors only.
20A max load per channel
192A max load per SCMR1220-NA
Connecting 0-10V Dimmer Loads
Temperature 32° F to 104° F (0° C to +40° C)
Humidity 0 to 95% non-condensing
The dimmer modules (SCMH1200-NA) will be pre-mounted
on the interior DIN rail per the order specifications. Each
0-10V dimmer requires a corresponding relay from the
SCMR1220-NA to turn the lighting load ON/OFF . This
mapping is performed during programming.
6
www.eaton.com/lighting
Line In
Neutral
Ground
Wiring Information:
1
5
Strip wire:
" to
"
2
8
Wire size: 10-12AWG
Solid/stranded copper only
*Note: Bring dedicated circuit to power
iLumin Plus lighting panel. Main power circuit
should not also power lighting.
iLumin Plus is pre-wired to power all modules
once main power is connected and energized.
For loads up to
20A
16A
12A
Prior to dimmer connection, test each load to verify there
are no shorts and 0-10V polarity is correct. Remove all wire
cuttings from the enclosure.
0-10V dimmers are number 1-12 on each SCMH1200-NA
module. Each 0-10V dimmer can be programmed to be
either source or sink the 10VDC, by default the dimmers are
sink type.
Relay Load Wiring Detail
Twelve: 20A Latching Relays
0-10V Dimmer Wiring Detail
Twelve: 0-10V Dimmers
Line In
Load Out
Wiring Information:
1
5
Strip wire:
" to
"
2
8
Wire size: 10-14AWG
Solid/stranded copper only
Use 75C wire insulation minimum
Load:
120-277VAC 20A per relay
Mag., Res, General Purpose
120V 20A Tungsten
120V 16A LED Ballast
277V 16A LED Ballast
Do not exceed 192A per module
Relay screw torque 1.1Nm
*Note: Branch Circuit over current protection
by others. Each relay has a 5K SCCR unless
protected by another device.
Class 1 Field Relay Terminals & Loads
20A max 10AWG min wire
16A max 12AWG min wire
12A max 14AWG min wire
Purple
Gray
Wiring Information:
1
5
Strip wire:
" to
"
2
8
Wire size: 18-14AWG
Solid/stranded copper only
Dimmer screw torque 1.1Nm
Suitable for Class 1 and Class 2
wiring per NFPA 70
Load:
100mA source/sink per channel
0-10VDC isolated (40 uA max per
circuit leakage to line)
*Note: Requires a relay (SCMR1220-NA) for
load On/Off capabilities.