3.2. To Re-Enter Quick Code
Configuration Mode
If you need to re-enter the 'Quick Configuration'
mode this can always be done as follows:-
1.
Power down the controller
2.
Hold
button down and power up the
controller again. Keep the button pressed until
Set 1 is displayed.
3.
The quick codes may then be set as described
previously
☺
Parameters may also be configured using a
deeper level of access. This is described in the
ELK/ETK Engineering Handbook Part No.
HA029065 which may be downloaded from
www.eroelectronic.com
☺
If the controller is started with the
held down, as described above, and the quick codes
are shown with dots (e.g. J.C.X.X.X), this indicates
that the controller has been re-configured in a deeper
level of access and, therefore, the quick codes may
not be valid.
Part number HA028438. Issue 3.0.
3.3. Pre-Configured Controller or
A brief start up sequence consists of a self test
during which the software version number is shown
followed briefly by the quick codes.
It will then proceed to Operator Level 1..
You will see the display shown below. It is called
the HOME display.
ETK example
The ALM beacon
will show red if
an alarm is
present.
The OP4 beacon
will be on if the
changeover relay
output is active
button
☺
If the quick codes do not appear during this start
up, it means that the controller has been configured
in a deeper level of access, see note in section 3.2.
The quick codes may then not be valid and are
therefore not shown.
Oct-05
Subsequent Starts
Measured
Temperature
Target
Temperature
(Setpoint)