AERMEC WSA Serie Manual Técnico De Instalación Y Mantenimiento página 11

Enfriadora agua
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

WSA - E
COOLING ONLY
Cooling capacity
Cooling capacity per circuit
Total input power
Evaporator water flow rate
Evaporator pressure drop
ENERGY INDICES
EER
EEC
ELECTRICAL DATA
Power supply
Total input current
Maximum current
FLA
Peak current
LRA
COMPRESSORS
Type
Number
Number per circuit
CAPACITY CONTROL
Std TV
Capacity control
Ele TV
EVAPORATOR
Type
Number
Hydraulic connections
SOUND DATA
Sound power
Sound pressure
DIMENSIONS - outdoor installation
Height (°)
Height (° - L)
Height (T)
Height (T - L)
Width
Length
WEIGHT empty
TECHNICAL DATA REFER TO THE NORM
EN14511 - 1 - 2 - 3
condensing system
- Processed water temperature
- Condenser inlet water temperature
- ¨t
0701
0801
0901
kW
163
192
212
-
-
-
-
kW
41
47
54
l/h
28040
33020
36460
18
18
17
kPa
W/W
3.89
4.09
3.93
A
A
A
V
72
81
90
A
124
144
162
A
163
192
229
A
no.
1
1
1
no./
1/1
1/1
1/1
no.
40-100 40-100 40-100 40-100 20-100 20-100 20-100 20-100 20-100 20-100 20-100
%
%
25-100 25-100 25-100 25-100 12.5-100 12.5-100 12.5-100 12.5-100 12.5-100 12.5-100 12.5-100
no.
1
1
1
V/3"
V/3"
V/3"
Type/ø
86.0
86.0
86.0
dB(A)
54.0
54.0
54.0
dB(A)
1775
1775
1775
mm
1775
1775
1775
mm
mm
2000
2000
2000
2120
2120
2120
mm
810
810
810
mm
mm
2960
2960
2960
kg
1251
1301
1357
- Sound pressure measured 10 m. away in the
open, with direction factor Q=2 according to
ISO 3744
7 °C
45 °C;
- Sound power The AERMEC sound power
5k
value is determined on the basis of measu-
1101
1402
1602
1802
263
326
385
428
163/163 192/193 214/214
66
82
93
108
45240
56070
66220
73620
21
33
37
38
3.98
3.98
4. 1 4
3.96
A
A
A
A
400V-3-50Hz
113
72
81
90
182
248
288
324
300
287
336
391
twin-screw
1
2
2
2
1/1
2/2
2/2
2/2
Plates
1
1
1
1
V/3"
V/3"
V/3"
V/3"
92.0
89.0
89.0
89.0
60.0
57.0
57.0
57.0
1775
1975
1975
2005
1775
2120
2120
2120
2000
2050
2050
2050
2120
2120
2120
2120
810
810
810
810
3360
2960
2960
2960
1788
2028
2097
2169
2002
2202
2502
481
539
601
269/270
120
132
146
82790
92710 103370 116270
40
45
49
4.00
4.08
4. 1 2
A
A
A
204
113
127
344
364
430
462
482
575
2
2
2
2/2
2/2
2/2
1
1
1
V/3"
V/3"
V/3"
93.0
95.0
95.0
61.0
63.0
63.0
1985
2065
2065
2120
2120
2120
2050
2065
2065
2120
2120
2120
810
810
810
3360
3360
3360
2598
3000
3095
rements taken in accordance with the ISO
9614-2 standard, in compliance with what is
required by the EUROVENT Certification
2802
676
159
59
4.25
A
136
430
575
2
2/2
1
V/3"
95.0
63.0
2065
2120
2065
2120
810
3360
3108
11

Publicidad

Capítulos

Tabla de contenido
loading