Ferroli ECONCEPT 51 A Instrucciones De Uso página 41

Ocultar thumbs Ver también para ECONCEPT 51 A:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

ECONCEPT 51 A
Hot water tank connection (Optional kit -)
The optional kit - is available for connection to an external hot water tank. The kit, which
comprises a circulating pump (ref. 130 - fig. 15), hot water tank probe (ref. S - fig. 15)
and plumbing fittings, must be installed inside the boiler according to the instructions
provided. Then connect to the fittings in the boiler.
130
10
I
210
179
10
209
fig. 15 - Hot water tank connection kit
209
DHW delivery
210
Hot water tank return
10
System delivery
11
System return
130
DHW pump kit
179
Non-return valves (not supplied)
B
Hot water tank (not supplied)
I
ISPESL safety devices (not supplied)
S
Hot water tank probe
A
Outlined connections to be carried out by the installer.
Plumbing circuit examples
Key of examples
I*
ISPESL safety devices (When required - not supplied)
D
Hydraulic separator (not supplied)
42
DHW temperature sensor (not supplied)
72
Room thermostat (not supplied)
72b
Room thermostat (not supplied)
95
3-way valve - with spring return: at rest on DHW side (not supplied)
130
Hot water tank circulating pump (not supplied)
138
External probe (not supplied)
139
Remote control (not supplied)
298
Cascade temperature sensor (not supplied)
306
Heating system circulating pump (not supplied)
307
Heating system second circulating pump (not supplied)
SM
Delivery probe (supplied with kit FZ4)
TS
Safety thermostat (not supplied)
PZ
Zone pump (not supplied)
FZ4
Zone regulator
S
B
11
cod. 3540S560 - 03/2009 (Rev. 00)
Parameters
Each system requires a different parametrisation. Follow the procedure for accessing the
two menus, given below; for the parameters to be modified, refer to the tables given
alongside the plumbing diagrams.
"Service Menu"
The card Service Menu is accessed by pressing the Reset button for 10 seconds.
Press the Heating buttons to select "tS", "In", "Hi" or "rE"". "tS" means Transparent Pa-
rameters Menu, "In" Information Menu, "Hi" History Menu, and "rE" History Menu Reset.
Select "tS" and press the Reset button.
The card is equipped with 29 transparent parameters also modifiable from Remote Con-
trol (Service Menu).
Press the Heating buttons to scroll the list of parameters in increasing or decreasing or-
der. Press the DHW buttons to modify the value of a parameter: the change will be au-
tomatically saved.
Press the Reset button to return to the Service Menu. Press the Reset button for 10 sec-
onds to exit to the card Service Menu.
"System Type Menu"
Press the Summer/Winter button for 10 seconds to access the card System Type Menu.
The card has 21 transparent parameters.
Press the Heating buttons to scroll the list of parameters in increasing or decreasing or-
der. Press the DHW buttons to modify the value of a parameter: the change will be au-
tomatically saved.
Press the Summer/Winter button for 10 seconds to exit the card System Type Menu.
One direct heating circuit
Check/Change parameter P02 of the "Transparent Parameters Menu" to 1.
Change parameter P.02 of the "System Type Menu" to 1.
Change parameter P.09 of the "System Type Menu" to 1.
138
One direct heating circuit and one DHW circuit with pump
Check/Change parameter P02 of the "Transparent Parameters Menu" to 2.
Change parameter P.02 of the "System Type Menu" to 1.
Change parameter P.09 of the "System Type Menu" to 1.
138
I*
298
306
D
fig. 16
42
I*
130
298
306
D
fig. 17
EN
72/139
A
72/139
B
41