L = 2.5 m) should be used. Fixed electrical connection of the bath should be prepared in zone I (the unit is located under
the tub), compensatory connection should be provided additionally. A marked compensatory clamp
the bath frame, to which a compensating cable should be connected 4mm².
Terminal made by the construction team should be in a form of a permanent distributive damp-resistant socket (IP 65, at
least 30 cm over the fl oor, in the area under the bathtub).When installing a bathtub attention should be paid to the parts
containing active elements (except for items supplied with low safe voltage, i.e. not exceeding 12 V) which must not be
available for persons located in bathtub.
The fact that bathtub is connected to the electricity must be noted in the warranty card with signature and seal of the
authorised person, which determines validity of the guarantee.

02.03.1 Protected Area

area 1
area 0
Do not use unit without positive
earth connection (PE,
Interrupt current connection before
opening!
area 2
60 cm
area 2
60 cm
)!
area 2
area 1
60 cm
area 0
L
1
L
2
L
3
N
PE
10A rccb
RCD 30 mA
Main switch in bathroom
(Position outside area 2
according to VDE 0100 Teil 701)
Equipotential bonding 4 mm²
is mounted on
GB