OPERATING CONDITIONS
Operating temperature:
Storage temperature:
Relative humidity:
ACCURACY
Accuracy on active energy:
Accuracy on reactive energy:
CE MARKING
The DIRIS A40/A41 complies with :
• The requirements of the European directive on electromagnetic compatibility (EMC) no. 89/336/CEE dated 3 May 1989,
modified by directive no. 92/31/CEE dated 28 April 1992 and by directive no. 93/68/CEE dated 22 July 1993.
• Low voltage directive no. 73/23/CEE dated 19 February 1973, modified by directive no. 93/68/CEE dated 22 July 1993.
ELECTROMAGNETIC COMPATIBILITY
Immunity to electrostatic discharges:
Immunity to radiated radio-frequency fields:
Immunity to electrical fast transients/bursts:
Immunity to impulse waves:
Immunity to conducted disturbances:
Immunity to power frequency magnetic fields:
Conducted and radiated emissions:
Immunity to voltage dips and short interruptions:
CLIMATE
Operating-temperature range:
Storage temperature range:
Humidity:
Saling fog:
MECHANICAL CHARACTERISTICS
Vibration from 10 to 50 Hz :
INSULATION
Installation category:
Degree of pollution:
Rated impulse withstand voltage:
Front face:
Electric security:
SOCOMEC - Réf. : 876 304 A
-10° to + 55°C (14° to 131°F)
-20° to + 85°C (-4° to 158°F)
95 %
CEI 62053-21 class 1
CEI 62053-23 class 2
IEC 61000-4-2 - Level III
IEC 61000-4-3 - Level III
IEC 61000-4-4 - Level IV
IEC 61000-4-5 - Level IV
IEC 61000-4-6 - Level III
IEC 61000-4-8 - Level IV
CISPR11 - Class B
IEC 61000-4-11
IEC 60068-2-1/IEC 60068-2-2
-10 °C to +55 °C
IEC 60068-2-1/IEC 60068-2-2
-20 °C to +85 °C
IEC 60068-2-30 - 95 %
IEC 60068-2-52 - 2,5 % NaCl
IEC 60068-2-6 - 2 g
For systems up to 700V AC (ph/ph)
III
2
IEC 60947-1 - V imp: 4 kV
Classe II
IEC 61010-1
DIRIS A40 / A41
TECHNICAL CHARACTERISTICS
45