PDU40TDUAL
Zero U Dual Independent Power Circuit
Power Distribution Unit (PDU)
Important Safety Instructions
SAVE THESE INSTRUCTIONS
This manual contains instructions and warnings that should be followed
during the installation, operation, and storage of this product. Failure to
heed these instructions and warnings will void the product warranty.
Important Warnings
• The PDU provides convenient multiple outlets distributed across two independent power circuits, but it
DOES NOT provide surge or line noise protection for connected equipment.
• The PDU is designed for indoor use only in a controlled environment away from excess moisture, temperature
extremes, conductive contaminants, dust or direct sunlight.
• Do not connect the PDU to an ungrounded outlet or extension cords or adapters that eliminate the connection
to ground.
• The power requirement for each piece of equipment connected to the PDU must not exceed the individual
outlet's load rating.
• The total power requirement for equipment connected to each of the two independent power circuits must not
exceed the maximum load rating for that circuit.
• Do not drill into or attempt to open any part of the PDU housing. There are no user-serviceable parts inside.
• Do not attempt to modify the PDU, including the input plugs and power cables.
• Do not attempt to use the PDU if any part of it becomes damaged.
• Do not attempt to mount the PDU to an insecure or unstable surface.
• Never attempt to install electrical equipment during a thunderstorm.
• Use of this equipment in life support applications where failure of this equipment can reasonably be expected
to cause the failure of the life support equipment or to significantly affect its safety or effectiveness is not
recommended. Do not use this equipment in the presence of a flammable anesthetic mixture with air, oxygen
or nitrous oxide.
Installation
1B
1A
1C
1A
Zero U Rack Configuration (Mounting Clips). Attach the three mounting clips supplied with the PDU
to the rack enclosure using the included hardware. The mounting clips should be attached along a vertical
plane at equidistant points which approximately correspond to the center and ends of the PDU. The exact
mounting configuration may vary depending on the rack and enclosure. If possible, use pre-existing
mounting points within the enclosure. Using an assistant, place a rear corner of the PDU at an inside edge
of the mounting clips, pivot the PDU toward the alternate inside edge and snap into place.
1B
Zero U Rack Configuration (Mounting Buttons). Attach the included mounting buttons to the PDU.
Position the PDU as desired in the rack enclosure, align the buttons with the rack mounting slots, and slide
the PDU into position.
1C
Wall or Under-Counter Configuration. Attach the three mounting clips supplied with the PDU to a wall
or similar flat, secure surface using the included hardware. The mounting clips should be attached along a
vertical or horizontal plane at equidistant points which approximately correspond to the center and ends of
the PDU. If possible, use pre-existing mounting points. Using an assistant, place a rear corner of the PDU
at an inside edge of the mounting clips, pivot the PDU toward the alternate inside edge and snap into place.
WARNING: Do not attempt to mount the PDU with the outlets facing downward; the mounting clips
are not designed to support the weight of the PDU in that manner.
Note: Regardless of configuration, the user must determine the fitness of hardware and procedures before
mounting. The PDU and included hardware are designed for common rack and rack enclosure types and
may not be appropriate for all applications.
PDU40TDUAL
Unidad de distribución de potencia (PDU) con
Circuito de potencia dual independiente de cero U
Instrucciones de seguridad importantes
GUARDE ESTAS INSTRUCCIONES
Este manual contiene instrucciones y advertencias que deben seguirse
durante la instalación, operación y almacenamiento de este producto. De
no seguirlas, se anulará la garantía del producto.
Advertencias importantes
• La PDU proporciona cómodas salidas múltiples distribuidas a través de dos circuitos de potencia
independientes, pero NO proporciona protección contra sobretensión o ruido en la línea al equipo conectado.
• La PDU está diseñada sólo para empleo en interiores en un ambiente controlado, lejos del exceso de humedad,
temperaturas extremas, contaminantes conductores, polvo o luz solar directa.
• No conecte la PDU a una salida sin conexión a tierra ni a cables de extensión o adaptadores que eliminen la
conexión a tierra.
• El requisito de potencia de cada equipo conectado a la PDU no debe exceder la capacidad de carga individual
de la salida.
• El requisito de potencia total para el equipo conectado a cada uno de los dos circuitos de potencia
independientes no debe exceder la máxima capacidad de carga para dicho circuito.
• No taladre ni trate de abrir ninguna parte de la cubierta de la PDU. No hay partes en su interior que requieran
mantenimiento por parte del usuario.
• No intente modificar la PDU, incluyendo los enchufes de entrada y los cables de alimentación.
• No intente usar la PDU si alguno de sus componentes está dañado.
• No intente montar la PDU en una superficie insegura o inestable.
• Nunca intente instalar equipos eléctricos durante una tormenta eléctrica.
• El uso de este equipo en aplicaciones de soporte de vida en donde la falla de este equipo pueda
razonablemente hacer suponer que causará fallas en el equipo de soporte de vida o afecte significativamente
su seguridad o efectividad, no está recomendado. No use este equipo en la presencia de una mezcla anestésica
inflamable con aire, oxigeno u óxido nitroso.
Owner's Manual
2
3
Copyright © 2008 Tripp Lite. All rights reserved.
Manual del propietario
Installation
(continued)
2
Attach each input plug of the PDU to a grounded outlet. The input plugs, power cords, breakers and
outlets are color-coded in black and gray to correspond to the two independent power circuits.
WARNING: Attach each input plug to a separate power circuit. Consult with the electrician at the
installation site if necessary.
3
Attach equipment to the PDU. Do not exceed the load rating for each circuit; distribute equipment
appropriately between the two circuits to obtain the maximum utility from the PDU.
4
Optional Installation. The PDU includes two adapters that convert the L5-20P input plugs to 5-20P input
plugs. Use both adapters, a single adapter or neither of the adapters. The adapters are optional; the PDU
will work properly without connecting the adapters. The adapters are not color-coded.
Features
1
2
1
NEMA L5-20P Input Plugs: The input plugs and associated power cords are color-coded to correspond
with each of the independent power circuits.
2
NEMA 5-20P Plug Adapters: The adapters convert the input plugs from NEMA L5-20P to NEMA 5-20P.
The adapters are not color-coded.
3
Circuit Breakers: If the current drawn by the equipment connected to the corresponding independent power
circuit exceeds that circuit's Maximum Load Rating for longer than a few seconds, a circuit breaker will trip
to prevent possible damage. When a circuit breaker trips, its plunger will pop up. Disconnect excess
equipment from the affected circuit and allow the breaker to cool one minute before depressing the plunger
to reset the breaker. The circuit breakers are color-coded to correspond with each of the independent power
circuits.
4
NEMA 5-15/20R Outlets: The outlets are color-coded to correspond with each of the independent power
circuits.
Limited Lifetime Warranty
Seller warrants this product, if used in accordance with all applicable instructions, to be free from original
defects in material and workmanship for its lifetime. If the product should prove defective in material or
4
workmanship within that period, Seller will repair or replace the product, at its sole discretion. Service under this
Warranty can only be obtained by Buyer delivering or shipping the product (with all shipping or delivery charges
prepaid) to: Tripp Lite, 1111 W. 35th Street, Chicago, IL 60609. Seller will pay return shipping charges. Call
Tripp Lite at (773) 869-1234 before sending any equipment back for repair.
THIS WARRANTY DOES NOT APPLY TO NORMAL WEAR OR TO DAMAGE RESULTING FROM
ACCIDENT, MISUSE, ABUSE OR NEGLECT. SELLER MAKES NO EXPRESS WARRANTIES OTHER
THAN THE WARRANTY EXPRESSLY SET FORTH HEREIN. EXCEPT TO THE EXTENT PROHIBITED
BY APPLICABLE LAW, ALL IMPLIED WARRANTIES, INCLUDING ALL WARRANTIES OF
MERCHANTABILITY OR FITNESS, ARE LIMITED IN DURATION TO THE WARRANTY PERIOD SET
FORTH ABOVE; THIS WARRANTY EXPRESSLY EXCLUDES ALL INCIDENTAL AND
CONSEQUENTIAL DAMAGES. (Some states do not allow limitations on how long an implied warranty lasts,
and some states do not allow the exclusion or limitation of incidental or consequential damages, so the above
limitations or exclusions may not apply to you. This Warranty gives you specific legal rights, and you may have
other rights which vary from jurisdiction to jurisdiction).
WARNING: The individual user should take care to determine prior to use whether this device is suitable,
adequate or safe for the use intended. Since individual applications are subject to great variation, the
manufacturer makes no representation or warranty as to the suitability or fitness of these devices for any specific
application.
WARRANTY REGISTRATION
Visit www.tripplite.com/warranty today to register the warranty for your new Tripp Lite product. You'll be automatically entered
into a drawing for a chance to win a FREE Tripp Lite product!*
* No purchase necessary. Void where prohibited. Some restrictions apply. See website for details.
Regulatory Compliance Identification Numbers
For the purpose of regulatory compliance certifications and identification, your Tripp Lite product has been assigned a unique
series number. The series number can be found on the product nameplate label, along with all required approval markings and
information. When requesting compliance information for this product, always refer to the series number. The series number
should not be confused with the marking name or model number of the product.
The policy of Tripp Lite is one of continuous improvement. Specifications are subject to change without notice.
Made in China.
Características
1
2
1
Enchufes de entrada NEMA L5-20P: Los enchufes de entrada y sus cordones de alimentación asociados,
están codificados en color para corresponder a los circuitos de potencia independientes.
2
Adaptadores de enchufes NEMA 5-20P: Estos adaptadores convierten los enchufes de entrada de NEMA
L5-20P a NEMA 5-20P. Los adaptadores no están codificados por color.
Interruptores automáticos: Si la corriente consumida por el equipo conectado al circuito de potencia
3
independiente respectivo excede la máxima capacidad de carga por más de unos cuantos segundos, el
interruptor automático disparará para evitar posibles daños. Cuando un interruptor automático dispara, su
émbolo se extiende. Desconecte el equipo en exceso del circuito afectado y permita que el interruptor
automático se enfríe un minuto antes de presionar el émbolo para restablecer el interruptor automático. Los
interruptores automáticos tienen código de color para corresponderse con cada uno de los circuitos de
potencia independientes.
4
Salidas NEMA 5-15/20R: Estas salidas tienen código de color para corresponderse con cada uno de los
circuitos de potencia independientes.
1111 W. 35th Street • Chicago, IL 60609 USA
(773) 869-1234 • www.tripplite.com
3
4
1111 W. 35th Street • Chicago, IL 60609 USA
(773) 869-1234 • www.tripplite.com
3
4