Install Vent System - Sears Kenmore W11040140A Instrucciones De Instalación

Secadora a gas y eléctrica
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Special provisions for mobile homes:
Exhaust vent must be securely fastened to a noncombustible
portion of mobile home and must not terminate beneath the
mobile home. Terminate exhaust vent outside.
Mobile Home Exhaust Installation
Determine vent path:
Select route that will provide straightest and most direct
path outdoors.
Plan installation to use fewest number of elbows and turns.
When using elbows or making turns, allow as much room
as possible.
Bend vent gradually to avoid kinking.
Use as few 90° turns as possible.
Determine vent length and elbows needed for best drying
performance:
Use following Vent System Chart to determine type of
vent material and hood combinations acceptable to use.
NOTE: Do not use vent runs longer than those specifi ed
in Vent System Chart. Exhaust systems longer than those
specifi ed will:
Shorten life of dryer.
Reduce performance, resulting in longer drying times
and increased energy usage.
The Vent System Chart provides venting requirements
that will help achieve best drying performance.
Vent System Chart
Number of
Type
90° turns
of vent
or elbows
0
Rigid metal
1
Rigid metal
2
Rigid metal
3
Rigid metal
4
Rigid metal
NOTE: Bottom exhaust installations have a 90° turn inside
the dryer. To determine maximum exhaust length, add one
90° turn to the chart.
18
Box/louvered
Angled
hoods
hoods
64 ft. (20 m)
58 ft. (17.7 m)
54 ft. (16.5 m)
48 ft. (14.6 m)
44 ft. (13.4 m)
38 ft. (11.6 m)
35 ft. (10.7 m)
29 ft. (8.8 m)
27 ft. (8.2 m)
21 ft. (6.4 m)

Install Vent System

1.
Install exhaust hood
Install exhaust hood and use caulking compound to seal
exterior wall opening around exhaust hood.
2.
Connect vent to exhaust hood
Vent must fi t over the exhaust hood. Secure vent to exhaust
hood with 4" (102 mm) clamp. Run vent to dryer location using
straightest path possible. Avoid 90° turns. Use clamps to seal
all joints. Do not use duct tape, screws, or other fastening
devices that extend into interior of vent to secure vent,
because they can catch lint.
12" min.
(305 mm)
12" min.
(305 mm)

Publicidad

Capítulos

Tabla de contenido

Solución de problemas

loading

Tabla de contenido