Operating data
a)
measurement category according to IEC 61010-1 ...................... CAT IV 600 V (III 1000 V)
b)
type of insulation ........................................................................................... double, Class II
c)
housing type .............................................................................................. double-composite
d)
degree of housing protection acc. to EN 60529 ............................................................. IP40
e)
pollution degree .................................................................................................................... 2
f)
opening of measurement clamp ........................................................................ 16 mm (0.6")
g)
power supply of the meter ............................................................... 2x LR6 AA 1.5 V battery
h)
diode test ...................................................................................... I = 0.15 mA, U
i)
continuity test ............................................................................ acoustic signal for R < 50 Ω
.................................................................................................. measuring current <0.35 mA
j)
indication for range exceeding .............................................................................OL symbol
k)
low battery indication ........................................................................................ symbol
l)
measurement rate ...................................................................3 measurements per second
m)
crest factor ........................................................................................................................ < 3
n)
range of the non-contact voltage detector ............................ 200...1000 V AC (50...60 Hz)
o)
input impedance .......................................................................... approx. 10 MΩ (V AC/DC)
p)
input impedance for Low Z ............................................................................... approx. 3 kΩ
q)
AC read-out ...............................................................................True RMS (A AC and V AC)
r)
AC bandwidth
▪ sine waves ...................................................................................................... 50...1000 Hz
▪ all waves.............................................................................................................. 50 / 60 Hz
s)
display .................................................................................................................. 4 digit LCD
...................................................................................... 6000 counts with function indicators
t)
dimensions ................................................................................................. 230 x 44 x 66 mm
u)
meter weight .................................................................................................................. 270 g
v)
meter weight (without batteries) .................................................................................... 223 g
w)
operating temperature ........................................................................................... +5..+40C
x)
operating humidity ............................ < 80% up to 31ºC decreasing linearly to 50% at 40ºC
y)
storage temperature ............................................................................................. -20..+60C
z)
storage humidity ........................................................................................................... < 80%
aa) drop test ............................................................................................................................ 2 m
bb) maximum operating altitude ....................................................................................... 2000 m
cc) Auto-Off function ............................................................................................ approx. 15 min
dd) compliance with the requirements of the following standards ............................EN 61010-1
........................................................................................ EN 61010-2-032, EN 61010-2-033
.......................................................................................................... EN 61243-3, EN 61326
ee) quality standard ...................................................................................................... ISO 9001
CMP-200F – USER MANUAL
< 3 V DC
0
57