Alarms; Problem Resolution - Zanotti ZN Serie Manual De Uso

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

12.4 Alarm s
On B oard version
Label
P1
P2
CA
dA
Rem ote P anel version
Label
E1
E2
AH1
AL1
OPd
HPA
Probe alarms "E1" and "E2" start some seconds after the fault in the related probe; they automatically stop some
seconds after the probe restarts normal operation. Check connections before replacing the probe.
Temperature alarms "AH1" and "AL1" automatically stop as soon as the thermostat temperature returns to
normal values and when defrost starts.
Failure
Environment probe
(Pb1)
End of de-frosting
probe
(Pb2)
HIGH/LOW pressure
alarm
Door open
Failure
Environment probe
(Pb1)
End of de-frosting
probe
(Pb2)
Alarm of HIGH
ambient
temperature
Alarm of LOW
ambient
temperature
Alarm door open
Pressure switch
alarm
Cause
• values outside the
operation range
• failed / shortcircuited /
open probe
• values outside the
operation range
• failed / shortcircuited /
open probe
• Overcoming of the
High/Low pressure value,
read by the corresponding
pressure switches (it is
over the highest allowed
differential value ).
Cause
• values outside the
operation range
• failed / shortcircuited /
open probe
• values outside the
operation range
• failed / shortcircuited /
open probe
•exceeding of the preset
temperature (over the
maximum preset
differential)
•exceeding of the preset
temperature (over the
minimum preset
differential)
• door open
• the pressure minimum
/maximum value has been
overcome (beyond the
minimum fixed differential
value)

Problem resolution

• check the type of probe
(NTC)
• check the wiring of probes
• replace the probe
• check the type of probe
(NTC)
• check the wiring of probes
• replace the probe
• Check the pressure switch
efficiency.
Check if the condenser is clean or if the
condenser fan is correctly working.
check if the coldroom has
the door open, its seal,
introduction of hot product
etc.
Problem resolution
• check the type of probe (NTC)
• check the wiring of probes
• replace the probe
• check the type of probe (NTC)
• check the wiring of probes
• replace the probe
• check the compressor operation.
check of cell (open doors), its seal,
introduction of hot product etc.
• check the operation of the control
unit.
• check pressure switch efficiency
• check if the condenser is clean
• check if there are refrigerant leaks
• check the condenser motor fan
functioning
30

Publicidad

Capítulos

Tabla de contenido
loading

Este manual también es adecuado para:

Zn0Zn1Zn2Zn3Zn2 pZn3 p

Tabla de contenido