TECHNICAL DATA
Power supply voltage ........................... 100-240Vac – 50/60Hz
Protection against electric shock ........ Class II
Installation type required ..................... Tipo X
Maximum consumption ....................... 0,7 W
Maximum current ................................ 0,01 A
Output................................................... 0-10 Vdc, 2-10 Vdc, maximum current 5mA
Relay .................................................... 3 A – 250Vac
Electric connection:
All cables used must fulfi l with IEC 60.227.
5 x terminals, supply and relay ............ Min. 0,25 mm2 cable / Máx. 1,5 mm² cable
5 x terminals, analogue output
and Modbus .......................................... Min. 0,25 mm2 cable / Máx. 1,0 mm² cable
Note: Same tool can be used for both terminals types
Measurement range:
CO2 ....................................................... 450-2000ppm
VOC ....................................................... 50-2000ppm (CO2 equivalent relative)
HR......................................................... 0-100%
Temp. .................................................... -10-50°C
Accuracy:
CO2 ....................................................... ± 50ppm
VOC ....................................................... ± 100ppm
HR......................................................... ± 2%
Temp. .................................................... ± 0,3°C
Ambient air humidity ........................... 10-95% without condensation
Case dimensions [height x width x deep.] .. 89 x 122 x 26 mm
ENVIRONMENTAL DATA
Ambient temperature .......................... 0-50°C
Covering classifi cation ......................... IP30
Pollution degree................................... 2
Weight .................................................. 150 g
M3 screw and 0,5 Nm torque
M2 screw and 0,3 Nm torque
13