Input registers (Read)
Register Discrete input
SetPoint
30001
30002
SetPoint Value
Light guide
30003
intensity
30004
Analog Output
30005
IAQ sensor TVOC
IAQ sensor CO2
30006
30007
Temp sensor
30008
Hum sensor
30009
CO2 sensor
Working mode
30010
48
Data type Range
16bits
0-100
16bits
0-2000
16bits
0-100
16bits
0-100
16bits
125-600
16bits
450-2000
16bits
-100-500
16bits
0-100
16bits
450-2000
1 : MF1
2 : MF2
16bits
3 : MF3
4 : MF4
Default Comments
-
P1 potentiometer position (%)
P1 potentiometer value (ppm
-
or HR)
-
P2 potentiometer position (%)
Analogue output (Vdc)
-
(Example: 56 = 5,6Vdc)
VOC sensor equivalent value
-
(ppb)
VOC sensor equivalent value
-
(ppm)
Temperature sensor value (°C)
-
(Example: 213 = 21,3°C)
-
Humidity sensor value (%HR)
-
CO2 sensor value (ppm)
-
Operating mode