Carel μChiller Manual Del Usuario página 88

Tabla de contenido

Publicidad

SPA
Index
Size
Ref.
48
1
E046
49
2
U031
51
1
U032
52
1
U033
53
1
U035
54
1
U037
55
2
U039
57
1
U040
58
1
U041
59
2
U042
61
1
U043
62
1
U044
63
1
U045
64
1
U046
65
1
U047
66
1
U048
67
1
U049
68
2
U050
70
2
U051
72
1
U052
73
2
U053
75
2
U054
78
1
DFr
79
2
U055
83
2
U056
85
2
U069
87
2
U070
89
2
U071
91
2
U072
93
2
U073
95
1
U074
96
1
U075
97
1
U076
98
1
U077
99
1
E001
100
1
E003
101
2
E004
103
2
E005
105
2
E006
107
2
E007
109
2
E008
111
2
E009
113
2
E010
115
2
E011
117
2
E012
119
2
E013
121
2
E014
123
2
E015
125
2
E016
127
2
E017
129
2
E018
131
2
E019
133
2
E020
135
2
E021
137
2
E022
139
2
E023
141
1
E024
142
1
E025
143
1
E026
144
1
E032
145
1
E033
146
1
E034
147
1
Hd00
148
1
Hd01
149
1
Hd02
153
1
C000
154
1
C002
155
1
C003
156
1
C005
157
1
C006
158
1
C008
159
1
C009
160
1
C011
88
Type
Min/Max
R/W
UoM
INT
1..24
R/W
REAL
0..99.9
R/W
K/R
INT
0..99
R/W
min
INT
0..999
R/W
s
INT
0..999
R/W
min
INT
0..999
R/W
s
REAL
0..999.9
R/W
INT
0..999
R/W
s
INT
0..99
R/W
s
REAL
0..999.9
R/W
INT
0..999
R/W
s
INT
0..99
R/W
s
INT
0..999
R/W
s
INT
0..99
R/W
s
INT
0..999
R/W
s
INT
0..999
R/W
s
INT
0..999
R/W
h
REAL
-999.9..999.9
R/W
°C/°F
REAL
0..999.9
R/W
K/R
INT
0..999
R/W
s
REAL
-999.9..999.9
R/W
°C/°F
REAL
0..99.9
R/W
K/R
INT
0..3
R/W
REAL
-99.9..99.9
R/W
K/R
REAL
-99.9..99.9
R/W
K/R
REAL
0..99.9
R/W
K/R
REAL
0..99.9
R/W
K/R
REAL
0..99.9
R/W
K/R
REAL
-999.9..999.9
R/W
°C/°F
REAL
0..99.9
R/W
K/R
INT
0..2
R/W
INT
0..2
R/W
INT
1..2
R/W
INT
0..2
R/W
INT
0..65535
R/W
Steps
INT
0..65535
R/W
Steps
REAL
-40..180
R/W
K/R
REAL
0..800
R/W
REAL
0..1000
R/W
s
REAL
0..800
R/W
s
REAL
-40..180
R/W
K/R
REAL
0..800
R/W
REAL
0..1000
R/W
s
REAL
0..800
R/W
s
REAL
-40..180
R/W
K/R
REAL
0..800
R/W
s
REAL
-40..180
R/W
K/R
REAL
0..800
R/W
s
REAL
-60..200
R/W
°C/°F
REAL
0..800
R/W
s
REAL
-60..200
R/W
°C/°F
REAL
0..800
R/W
s
REAL
-60..200
R/W
°C/°F
REAL
0..800
R/W
s
REAL
-60..200
R/W
°C/°F
REAL
0..800
R/W
s
INT
0..18000
R/W
s
INT
0..18000
R/W
s
INT
0..18000
R/W
s
INT
0..100
R/W
%
INT
0..100
R/W
%
INT
0..18000
R/W
s
INT
1..247
R/W
INT
3..7
R/W
INT
0..5
R/W
INT
0..999
R/W
h
INT
0..2
R/W
INT
0..999
R/W
h
INT
0..2
R/W
INT
0..999
R/W
h
INT
0..2
R/W
INT
0..999
R/W
h
INT
0..2
R/W
Description
E046 - ExV valve type for EVD EVO (1=CAREL EXV, ...)
U031 - High water temp. setpoint offset
U032 - High water temp. startup delay
U033 - High water temp.run delay
U035 - Changeover delay time
U037 - Delay time between Startup PID and Run PID
U039 - Startup PID Kp
U040 - Startup PID Ti
U041 - Startup PID Td
U042 - Run PID Kp
U043 - Run PID Ti
U044 - Run PID Td
U045 - User pump flow alarm startup delay
U046 - User pump flow alarm run delay
U047 - Compr. delay ON since the user pump ON
U048 - User pump delay OFF since the compr. OFF
U049 - User pump rotation time
U050 - Antifreeze user alarm threshold
U051 - Antifreeze user alarm differential
U052 - Antifreeze user alarm delay time at 1K below threshold
U053 - Antifreeze (with unit OFF) setpoint
U054 - Antifreeze (with unit OFF) differential
DFr - Force manual defrost (0= None, 1= Force defrost on circ. 1, 2= Force defrost
on circ. 2, 3= Force defrost on all circuits)
U055 - Probe offset of return water temp. from user
U056 - Probe offset of delivery water temp. to user
U069 - Delta temp. to activate Free-Cooling
U070 - Free-Cooling ON/OFF hysteresis
U071 - Delta temp. Free-Cooling design (to reach unit nominal capacity)
U072 - Free-Cooling limit threshold (used to close FC valve: because FC gives water
with temp. very low)
U073 - Free-Cooling limit differential
U074 - Free-Cooling type (0=Air, 1=Remote air coil, 2=Water)
U075 - Antifreeze type (0=Heater, 1=Pump, 2=Heater-Pump)
U076 - User pump number
U077 - Unit type (0=CH, 1=HP, 2=CH/HP)
E001 - ExV circ.1 manual mode steps
E003 - ExV circ.2 manual mode steps
E004 - ExV SH setpoint in cool
E005 - ExV SH regulation Kp in cool
E006 - ExV SH regulation Ti in cool
E007 - ExV SH regulation Td in cool
E008 - ExV SH setpoint in heat
E009 - ExV SH regulation Kp in heat
E010 - ExV SH regulation Ti in heat
E011 - ExV SH regulation Td in heat
E012 - ExV low SH threshold in cool
E013 - ExV low SH Ti in cool
E014 - ExV low SH threshold in heat
E015 - ExV low SH Ti in heat
E016 - ExV LOP regulation threshold in cool
E017 - ExV LOP regulation Ti in cool
E018 - ExV LOP regulation threshold in heat
E019 - EEV LOP regulation Ti in heat
E020 - ExV MOP regulation threshold in cool
E021 - ExV MOP regulation Ti in cool
E022 - ExV MOP regulation threshold in heat
E023 - ExV MOP regulation Ti in heat
E024 - ExV low SH alarm delay time
E025 - ExV LOP alarm delay time
E026 - ExV MOP alarm delay time
E032 - ExV startup valve opening % (capacity ratio EVAP / EEV) in cool
E033 - ExV startup valve opening % (capacity ratio EVAP / EEV) in heat
E034 - ExV regulation delay after pre-positioning
Hd00 - BMS port serial address
Hd01 - BMS port baud rate (3=9600, 4=19200, 5=38400, 6=57600, 7=115200)
Hd02 - BMS port network settings (0=8- NONE- 1, 1=8- NONE- 2, 2=8- EVEN- 1,
3=8-EVEN-2, 4=8-ODD-1, 5=8-ODD-2)
C000 - Compr.1 circ.1 maintenance hour threshold (x100)
C002 - Compr.1 circ.1 manual mode (0=AUTO, 1=OFF, 2=ON)
C003 - Compr.2 circ.1 maintenance hour threshold (x100)
C005 - Compr.2 circ.1 manual mode (0=AUTO, 1=OFF, 2=ON)
C006 - Compr.1 circ.2 maintenance hour threshold (x100)
C008 - Compr.1 circ.2 manual mode (0=AUTO, 1=OFF, 2=ON)
C009 - Compr.2 circ.2 maintenance hour threshold (x100)
C011 - Compr.2 circ.2 manual mode (0=AUTO, 1=OFF, 2=ON)
μchiller +0300053ES rel. 2.0 - 07.07.2020