6 Care
6.1
Filter
Operation that can be done by the user. However, you are advised to get it done by a professional.
The VMI® PULSE'R Prestige 2 unit is equipped with a grade G4 filter.
The VMI® PULSE'R Prestige 2 + unit is equipped with a grade F7 filter or grade F7+G4 filters for certain
types of installations.
To ensure optimum air quality and correct functioning of the VMI® unit, the filter must be regularly
changed.
Refer to step 12 of the assembly instructions when changing the URBAN VMI® filter
Changing the filter
Order a new filter preferably from the installer or otherwise from VENTILAIRSEC.
Access the VMI® unit.
Manually unscrew the 2 plastic head screws on the filter compartment.
For the Prestige Galbé models, remove the filter drawer.
Remove the old filter.
WARNING: do not insert anything in the machine apart from the new filter.
Insert the new filter.
o For a G4 filter: the blue part of the filter must be facing the outside of the machine.
o For an F7 filter: the tab on the filter must be pointing towards the outside of the VMI®
unit.
The new filter must be quickly inserted after the old one is removed.
Screw down the 2 plastic head screws.
Reset the filter counter on the remote control (see the filter status screen).
WARNING: when changing the filter, only the drawer must be removed. You may get an electric shock,
get burnt or cut yourself if you open the housing.
48