Gossen MetraWatt MAVOWATT Serie Guía De Uso página 55

Analizadores de redes
Tabla de contenido

Publicidad

Description
Volts Over-
Deviation
User Specified
Frequencies
Main Signaling
Frequencies
Individual
Harmonic
Voltages
0-127
0=DC
Individual Harmonic
Current h0-63
h0=DC
* from 3 % to 15 % of Udin, +/- 5 % of measured value, from 1 % to 3 % of Udin, +/- 0.15 % of Udin
GMC-I Messtechnik GmbH
Abbreviation
Wiring Configuration
HVodev-a
All
HVodev-b
HVodev-c
HVodev-d
HVodev-ab
HVodev-bc
HVodev-ca
All
Volts only
Volts
Current
MAVOWATT 230, 240, 270 & 270-400
Formula
If result is < V nom then
value is 0
Where:
V nom is Declared
Nominal Voltage
V rms is 200 ms RMS
Per
61000-4-30
5 individually recorded
frequencies derived
from DFT expansion.
User selectable in 5 Hz
increments.
5 individually recorded
frequencies derived
from DFT expansion.
User selectable in 5 Hz
increments.
Computed according to
61000-4-7 using DFT
over 200 mS window
aggregated to selected
journal inter- val as
RMS
Computed according to
61000-4-7 using DFT
over 200 mS window
aggregated to selected
journal inter- val as
RMS
Units
Precision
%
+/- 1 %
Volts
+/- .2 %
or
Amps
Volts
+/- 5 % *
or
Amps
Volts
+/- 5 %
Amps
+/- 5 %
55

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Mavowatt 230Mavowatt 240Mavowatt 270Mavowatt 400

Tabla de contenido