Descargar Imprimir esta página

Danfoss AK-RC 101 Manual Del Usuario página 6

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

Alarm codes
In the event of any anomalies, the OPTYMA
warns the operator by displaying alarm codes and
sounding the warning buzzer inside the control
Alarm code
Possible cause
E0
Cold room temperature sensor not working
properly
E1
Defrost sensor not working properly
(In this case defrosts will last time d3)
E2
Eeprom alarm
An EEPROM memory alarm has been detected
(All outputs except the alarm are deactivated)
E8
Man-in-cold-room alarm
Ec
Compressor protection tripped (e.g. thermal
protection or max. pressure switch)
(All outputs except the alarm– where
applicable – are deactivated)
Ed
Open door - alarm (Open door and tdo-time
has expired)
Temperature
Minimum or maximum temperature alarm.
shown on
The temperature inside the cold room has
display is
exceeded the min. or max. temperature
flashing
alarm setting (see variables A1 and A2, user
programming level)
6
Control
panel. If an alarm is tripped, the display will show one
TM
of the following messages:
Solution
• Check that the cold room temperature
sensor is working properly.
• If the problem persists, replace the sensor.
• Check that the defrost sensor is working
properly.
• If the problem persists, replace the sensor.
• Switch unit off and back on again.
• Reset the alarm input inside the cold room
• Check that compressor is working properly.
• Check compressor absorption.
• If the problem persists, contact the
technical assistance service.
Check door / door contact
• Check that the compressor is working
properly.
• Sensor not reading temperature correctly or
compressor start/stop control not working.
RI8NN55K
Instructions
© Danfoss 2015/08
AK-RC 101 / 103

Publicidad

loading

Este manual también es adecuado para:

Ak-rc 103