Details about the MCM10 module
2.6
Specification
2.6.1
General information
Designation
Weight (excluding packaging)
Rated voltage MCM10
Frequency
Maximum on-site fuse protection on
the power supply side
Rated output MCM10
Rated voltage BUS
Internal appliance fuse, heating
circuit pump output
Measuring range, flow temperature
sensor
Measuring range, outside
temperature sensor
Permissible ambient temperature
MCM10
Permissible ambient temperature,
flow temperature sensor
Permissible ambient temperature,
outside temperature sensor
Maximum cable length, EMS BUS
connections
Maximum length of sensor leads
EMC suppression level to
IP rating
Tab. 2 General information
2.6.2
Dimensions
62
235
7 746 800 090-02.1O
Fig. 2
Dimensions
58
Unit
Values
kg
0.8
V AC
230
Hz
50 ... 60
A
16
W
5
V DC
15
AT
2.5 A, ceramic,
filled with sand
°C
0 ... 100
°C
– 40 ... 50
°C
0 ... 50
°C
0 ... 100
°C
– 50 ... 100
m
(
tab. 7, page 65)
m
(
tab. 8, page 65)
EN 60730
IPX4D
62
MCM10