1. Technical Data
Enclosure heaters without fans
Model No. SK
3105.310
W
45
Dimensions mm
H
120
D
46
Hole distance
A
mm
42
Rated operating
110 – 240 V, 50/60
voltage Volt, Hz
Continuous thermal
8 – 10 W
output at T
= 10˚C
u
Pre-fuse T
2 A
Enclosure heaters with fans
Model No. SK 110 V
Model No. SK 230 V
Dimensions mm
Hole distance
A
mm
Rated operating voltage Volt, Hz
Continuous thermal output
at T
= 10˚C
u
Pre-fuse gG for 110 V
Pre-fuse gG for 230 V
1)
Output with fan.
Special voltages available on request. We reserve the right to make technical modifications.
2. Mounting
The panel heater is fitted vertically, i.e. with
the connection terminal or fan facing down-
wards. To permit the required convection, a
minimum clearance to the adjacent compo-
nents must be observed. A safety clearance
of at least 300 mm must be left above the
heater in the case of heaters with fans, and
100 mm for heaters without fans. (For both
a thermal safety clearance to the sides of
60 mm and 100 mm at the bottom is
required).
If these clearances are observed, the ambi-
ent temperature does not rise above 65˚C.
2.1 Snap-type fastening onto a 35 mm
support rail DIN EN 50 022 (Fig. 1.1).
2.2 Screw fastening onto the mounting plate
(Fig. 1.2).
RITTAL enclosure heater assembly instructions
3105.320
3105.330
3105.340
45
64
64
120
155
155
46
56
56
18 – 20 W
23 – 30 W
49 – 50 W
4 A
3105.210
3105.180
W
142
H
170
D
101
124
110 or 240 V, 50/60
1)
250 W
4 A
4 A
It should be ensured that the heater and
connection cables are mounted firmly and
securely.
Electric cables must not touch the body of the
heater fan and must not be routed directly
past the hot air outlet. The heater must
not be mounted in the vicinity of flammable
materials.
Notes
3105.350
3105.360
64
90
230
165
56
75
60
63 – 75 W
86 – 100 W 130 – 150 W
3105.220
3105.230
3105.190
3105.200
142
142
170
170
101
101
1)
400 W
800 W
6 A
10 A
6 A
6 A
EN
3105.370
90
180
75
1)
5