USER INTERFACE BOARD
USER INTERFACE BOARD
Drive
Settings /
Protection
Pressure
Adjustment
Pressure
Transducer
Connection
Table 2: Controller, Breaker, Generator Sizing
3 Phase Motor
Controller Model ②
HP
Voltage ①
BF20
230
¾
200
230
1
200
230
1½
200
230
2
200
230
3
200
230
5
200
8
Figure 3: UIB (User Interface Board)
Circuit
Generator ④
BF30
BF50
Breaker ③
15
20
30
40
50
TRANSDUCER
JUMPER
Table 3: Service Factor Amps 3 Phase Motors
HP
CentriPro
(VA)
2900
¾
1
3500
1½
2
4400
3
5
6100
NOTES:
① Motor Nameplate must be the same as supply voltage.
② Shaded areas indicate which controller models can be used with which
8100
motors. Lighter shading indicates combinations where controller will limit
peak performance to 85% of catalog value for pump/motor.
13300
③ Circuit Breaker or Dual Element Time Delay Fuse Size (Amps) protecting
branch circuit supplying controller.
④ Minimum size of single phase 240 V generator required.
Current Limit Dial
(Motor Overload
Protection)
Switch Input (Over
Pressure Protec-
tion, Level Control)
230 Volt, 3Ø
200 Volt, 3Ø
Franklin
CentriPro
SFA
SFA
SFA
4.0
3.8
4.5
4.7
4.7
5.5
6.1
5.9
7.2
7.6
8.1
8.8
10.1
10.9
12
17.5
17.8
20.2
Franklin
SFA
4.4
5.4
6.8
9.3
12.5
20.5