Serial Device Server
This table shows the maximum recommended distances when a RS232 data transmission cable of low capacity is used.
It is also advisable to use a shielded type cable.
The communication used is a null modem type (without flow control). This kind of connection is the most used in RS232
links. Uses only 3 wires to stablish full duplex connections between devices.
TG-IP1-SEC Connections
RS232 Tx
RS232 Rx
Gnd
The connection between TG-IP1 SEC device and the host equipment is made through the provided cable assemblies.
RS485 Assembly Diagram
1
2
3
4
5
6
7
8
TG-IP1 SEC Side
TTL-UART Assembly Diagram
GND
1
TX
2
RX
3
+24V
4
TG-IP1 SEC Side
Note that +24V wire on the TTL-UART Assembly cable is intended to supply the TG-IP1_SEC device directly from compatible fire panels,
without need to supply the device on the POWER IN connector.
3.1.1
RS485 Port
The RS232 port of the TG-IP1-SEC allows to interconnect devices through half duplex serial links up to a maximum
distance between 600m and 1200m depending on the speed of the port used (according to EIA/TIA RS-485A):
Baudrate (baud)
115200
57600
38400
19200
9600
4800
2400
TG-IP1-SEC_User Manual
TG-IP1-SEC
GND
Max. distance (meters)
600
1000
1200
Device connections
Rx RS232
Tx RS232
Gnd
TX
RX
GND
B
A
Host Equipment Side
Host Equipment Side
8
RS-232
5
3
9
4
2
8
3
7
5
2
6
1
GND
4
RX
3
TX
2
+24V
1
HLSI_MN-DT-1412_01 - Oct. 2017