Serial Device Server
This table shows the maximum recommended distances when a RS485 data transmission cable of low capacity 120Ohm
cable is used. It is also advisable to use a shielded type cable.
TG-IP1-SEC Connections
RS485 A
RS485 B
Gnd
Note that TG_IP1_SEC RS485 Port has a fixed source 120Ohm load. The user must decide the need of the end bus 120Ohm load,
depending on the fire panel RS485 interface.
RS485 Assembly Diagram
1
2
3
4
5
6
7
8
TG-IP1 SEC Side

CONFIGURATION

4 Local configurations in the TG-IP1-SEC
The TG-IP1-SEC interface requires minimum local configurations to work. It is only necessary to configure the Network
Adjustments and/or the RS232 serial port parameters.
These configurations are made through the incorporated web interface in the TG-IP1-SEC. In a compatible web browser
(HTML5),type the default IP address of TG-IP1-SEC, which is 192.168.1.253. Next a user name and a password will be
required. The default ones are admin and 123456. These credentials must be modified later from the
'Access Configuration' page for greater security.
Navigating the TG-IP1-SEC web interface
Access to the Status Monitor page.
Access to the Network Setup page.
Access to the UART Setup page.
Access to the Access Configuration page.
Access to the Device Information page.
COMMAND: Save Changes.
COMMAND: Reset Device.
TG-IP1-SEC_User Manual
TG-IP1-SEC
Device connections
RS485 A
RS485 B
Gnd
B
A
GND
9
RS-232
5
TX
3
9
4
RX
2
8
3
7
GND
5
2
6
1
Host Equipment Side