Mitsubishi Electric Ecodan EHST20 serie Para El Instalador página 26

Ocultar thumbs Ver también para Ecodan EHST20 serie:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 242
4
installation
Option 2: Cylinder unit powered by independent source.
If the cylinder unit and outdoor unit have separate power supplies, the following
requirements MUST be carried out:
• Change the connector connections in the control and electrical box of
the cylinder unit (see Figure 4.6.3)
• turn the outdoor unit diP switch SW8-3 to On
• turn on the outdoor unit BeFOre the cylinder unit.
<1 phase>
Power
supply
~/N
Earth
230V
leakage
50Hz
circuit
breaker
*1
*1 If the installed earth leakage circuit breaker does not have an over-current protection function, install a breaker with that function along the same power
line.
*2 Affix label B that is included with the manuals near each wiring diagram for cylinder unit and outdoor units.
description
Booster heater (Primary circuit)
Immersion heater (DHW tank)
Cylinder unit power supply
Cylinder unit input capacity
Main switch (Breaker)
Cylinder unit power supply
Cylinder unit power supply earth
Cylinder unit - Outdoor unit
Cylinder unit - Outdoor unit earth
Cylinder unit L - N
Cylinder unit - Outdoor unit S1 - S2
Cylinder unit - Outdoor unit S2 - S3
*1. A breaker with at least 3.0 mm contact separation in each pole shall be provided. Use earth leakage breaker (NV).
The breaker shall be provided to ensure disconnection of all active phase conductors of the supply.
*2. Max. 120 m
*3. The values given in the table above are not always measured against the ground value.
note:
1. Wiring size must comply with the applicable local and national codes.
2. Indoor unit/outdoor unit connecting cords shall not be lighter than polychloroprene sheathed flexible cord. (Design 60245 IEC 57)
Indoor unit power supply cords shall not be lighter than polychloroprene sheathed flexible cord. (Design 60227 IEC 53)
3. install an earth longer than other cables.
4. Please keep enough output capacity of power supply for each heater. the lack of the power supply capacity might cause
chattering.
25
Power
supply
Earth
~/N
leakage
230V
circuit
50Hz
breaker
*1
Outdoor unit
Wiring
L
circuit
breaker
N
or
Isolating
switch
Power
supply
~/N
230V
50Hz
Power
supply
~/N
230V
50Hz
<Figure 4.6.4>
Electrical connections 1 phase
Power supply
Capacity (indoor unit ref.) Breaker
~/N 230 V 50 Hz
2 kW (EHPT20X-VM2H*)
6 kW (EH*T20X-VM6**)
~/N 230 V 50 Hz
3 kW (EH*T20*-VM*H*)
~/N 230 V 50 Hz
*1
2 × Min. 1.5
1 × Min. 1.5
*2
2 × Min. 0.3
*3
*3
*3
Initial settings
(Power supplied by
outdoor unit)
Modified settings
(Separate power
supply to the cylinder
unit)
Cylinder unit
TB1
Wiring
L
To control
circuit
board
breaker
N
or
Isolating
switch
S1
S1
S2
S2
S3
S3
ECB1
For
Wiring
booster
L
heater
circuit
(Primary circuit)
breaker
N
or
Isolating
switch
ECB2
For
Wiring
Immersion
L
circuit
heater
breaker
(DHW tank)
N
or
Isolating
switch
Wiring
16 A *1
2.5 mm²
32 A *1
6.0 mm²
16 A *1
2.5 mm²
16 A
230V AC
24V DC
L
N
Black
CN01
Cylinder unit
S1
control board
S2
S3
L
N
Black
CN01
Cylinder unit
S1
control board
S2
S3
<Figure 4.6.3>