BLUEHELIX PRO C
Fault code
Fault
F39
External probe fault
A41
Sensor positioning
A42
Heating sensor fault
Exchanger protection
F43
activation
A44
Sensor positioning
F52
Heating sensor fault
Controller fault
A61
ABM03C
No communication
A62
between controller and
gas valve
A63
F64
Controller fault
A65
ABM03C
F66
A23
A24
F20
F21
Card parameter fault
A26
F40
F47
5. TECHNICAL DATA AND CHARACTERISTICS
196
350
81
35
278
221
42
10
8
44
fig. 26 - General view
Possible cause
Cure
Probe damaged or wiring
Check the wiring or replace the sen-
shorted
sor
Probe disconnected after
Reconnect the external probe or dis-
activating the sliding
able the sliding temperature
temperature
Heating sensor detached
Check the correct positioning and
from pipe
operation of the heating sensor
Sensor damaged
Replace the sensor
No system H
O circula-
2
Check the circulating pump
tion
Air in the system
Vent the system
DHW sensor detached
Check the correct positioning and
from pipe
operation of the DHW sensor
Sensor damaged
Replace the sensor
Controller internal error
Check the earth connection and
ABM03C
replace the controller if necessary.
Connect the controller to the gas
Controller not connected
valve
Valve damaged
Replace the valve
Controller internal error
Check the earth connection and
ABM03C
replace the controller if necessary.
Wrong card parameter
Check the card parameter and mod-
setting
ify it if necessary.
7
9
11
39
74
136
37
cod. 3541F552 - Rev. 00 - 03/2016
Table. 9 - Legend - figures cap. 5
7 Gas inlet
8 Domestic hot water outlet
9 Cold water inlet
10 System delivery
11 System return
14 Pressure relief valve
16 Fan
32 Heating circulating pump
35 Air separator
36 Automatic air vent
37 Cold water inlet filter
39 Flow regulator
42 DHW temperature sensor
44 Gas valve
56 Expansion tank
72 Room thermostat (not supplied)
74 System filling cock
81 Ionisation/ignition electrode
35
278
191
56
221
186
193
10
14
36
114
32
104 Fuse
114 Water pressure switch
136 Flow meter
138 External probe (optional)
139 Remote timer control (optional)
154 Condensate drain pipe
186 Return sensor
191 Fume temperature sensor
193 Trap
196 Condensate tray
221 Bypass cock
256 Modulating heating circulating pump signal
278 Double sensor (Safety + Heating)
340 Bypass pipe
350 Fan/Burner assembly
A ON/OFF switch (configurable)
193
154
74
340
39
136
42
37
8
9
fig. 27 - Hydraulic circuit
EN
186
56
114
36
14
32
11