Main Parts; Airflow Alarm - Control Box; Technical Data - Nederman Airflow Alarm Kit Manual De Instrucciones

Ocultar thumbs Ver también para Airflow Alarm Kit:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

3.3

Main parts

See figure 1. The Airflow alarm kit consists of:
1.

Airflow Alarm - Control box.

2.
Pressure switch. Available as a standard model, and an ATEX approved
model for zone 2/22.
3.
Protection filter.
4.
Rubber fitting.
5.
Flashlight (optional).
6.
Cable gland (optional).
3.3.1
Airflow Alarm - Control box
See figure 2. The Airflow Alarm contains a terminal block that includes
connections to:
1.
85-230 VAC power supply (Phase 1). Signal in from fan to activate
monitoring.
2.
85-230 VAC power supply (Phase 2). Power in to Airflow Alarm.
3.
External connection to central surveillance (Optional).
4.
Pressure switch.
5.
External Airflow Alarm devices such as a flashlight.
NOTE! Drill an extra hole and install a cable gland if the Control box is to be
directly connected to both a flashlight and to central surveillance. See figure
1(6).
3.4

Technical data

Part
Supply PSU1
Supply PSU2
Pressure switch
12 V DC out alarm
Alarm relay
9V battery
Fuse
Dimensions
Operating temperature
IP Class Control box
IP Class Pressure Switch Standard
IP Class Pressure Switch ATEX
Description
85 - 230V AC, 50-60Hz, max. 13A Fuse
85 - 230V AC, 50-60Hz, max. 13A Fuse
External contact must be below 100 Ohm
12 V DC maximum 200 mA
Maximum 8A AC1 250 VAC
6LR61, non rechargeable
5 x 20 T500mA
120 mm x 170 mm x 60 mm
0 - 50 °C
IP54
IP54
IP65, ATEX model approved for zone 2/22.