Wiring The Relays - Leviton DMX Serie Guia De Instalacion

Cubren los gabinetes 8, 24 & 48 relevadores con un modulo de control maestro, software revision 2.00 y superior
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Wiring the Relays

Step 1:
Connect the line (feed/circuit breaker) side of the circuit to the "input"
terminal(s) on the relay card.
Step 2:
Connect the load side of the circuit to the "output" terminal(s) on the
relay card.
Step 3:
Please note that relay card terminals accept the following wire sizes:
Relay Type
Wire
(Part #)
Size
Standard
20-8
Solid or
1-Pole relay
AWG
Stranded
module
Copper
(RELAY-STD)
2-Pole relay
20-6
Solid or
module
AWG
Stranded
(RELAY-2PL)
Copper
347V relay
20-6
Solid or
module
AWG
Stranded
(RELAY-347)
Copper
Latching
20-8
Solid or
Relay Module
AWG
Stranded
(RELAY-LAT)
Copper
NOTE:
Circuit neutrals may follow the path of the line/load conductors through the
relay panel or the line/load conductors may pass back to the panel board to
be joined with the neutral to the load.
The diagrams on the following pages show how to wire the relay circuits.
WARNING: MISWIRING THE RELAY MODULES WILL CAUSE DAMAGE TO THE
RELAY MODULE, THE RELAY CABINET, AND POSSIBLY OTHER SYSTEMS
Wiring Diagram for Standard 1 Pole Relay Card
8
Wire
Max
Torque
Type
Voltage
7 in-lbs
277V
20.5 in-lbs
277V
per pole
(480V)
20.5 in-lbs
347V
7 in-lbs
277V
347V
Wire Sizes & Capacities for Relays
(latching relay card similar)
Tungsten
Ballast
Motor Rating
Rating
Rating
(120V/277V)
(120V)
20A
20A
1HP/2HP
20A
2HP
20A
20A
20A
1HP/2HP
15A
Load
Line (from Distribution Panel)
Inductive
Ballast,
Transformer,
HID Rating
20A
20A
20A
20A
15A

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Dmx 8Dmx 24Dmx 48

Tabla de contenido