Fleck 3200 NT Manual De Uso página 29

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

1.11
1.12
E
TO
N
1.17
G
L
I
S
H
1.18
TO
1.20
28
3 - PROGRAMMATION 3200 NT
Calendar forcing
This parameter allows forcing a regeneration. It determines the maximum number of days the
valve will be in service without regenerating independently from the volume of water used. For
a timeclock valve, this value must be set. For metered valves, it will regenerate once the amount
of days reached at the same time as the previous regeneration (meter immediate) or at a preset
time (meter delayed) unless the meter triggers a regeneration before.
Timeclock valve: 1 to 99 days
Metered valve : OFF, 1 to 99 days
Ex.: regeneration every 7 days
Function cancelled
Programmation of the cycle times of the
regeneration
This parameter allows setting the cycle times of the regeneration. 6 cycles can be programmed.
The first digit indicates the cycle number being programmed. 6 cycles can be programmed. The
display allows setting the specific time of each cycle. If a cycle is set to OFF, the next cycles will
not be displayed.
Ex.: cycle #1 backwash
cycle #2 brine draw/slow rinse
cycle #5 off
cycle #6 not displayed
Programmation of the auxiliary outlets [AroF],
[cPoF]
The two next displays correspond to a serie of settings used to program optional auxiliary outlet
signals. The first parameter allows the on/off feeding of the outlet during the regeneration. The
second pilots the outlet during service based on a volume of water. The second display is only
visualised with metered systems.
Notice: if two options are used, it is up to the softener manufacturer to supply the necessary
switching logic to pilot the two appliances using the same auxiliary outlet.
Auxiliary outlet [AroF]
This parameter is composed of two displays. The first one is used to activate the outlet feeding.
The second display is used to deactivate the outlet feeding. Displaying OFF cancels this function
An "S" indication on the second display (feeding deactivation) will lock the outlet as soon as the
valve goes back in service. All the settings are in minutes. The time setting of the auxiliary should
not be longer than the total regeneration time.
- cancelled option
- outlet activated when regeneration starts
- outlet deactivated when valve goes back in service ( total of cycle times)
Ex.: activate the contact 10min for 15 minutes
- outlet activated 10 min after regeneration start
- outlet deactivated
Auxiliary outlet [cPoF]
This parameter is composed of two displays. The first one is used to set a volume that triggers
the closure. The second is used for setting the outlet closing time (in seconds).
- option cancelled
Ex.: activate the outlet every 200 litres during 60 seconds
- frequency every 200 litres
- activation time
[A- - 7]
[AOFF]
[1- 10]
[2- 60]
[ 5 0 F F ]
[AroF]
[S- - 0]
[E- 92]
[S- 10]
[E- 25]
[cPoF]
[u200]
[t- 60]
3200 NT

Publicidad

Tabla de contenido
loading

Tabla de contenido