SMOKE ALARM
INSTALLATION POSITION FOR INCLINED ROOFS
10 cm
90 cm
50 cm
10 cm
60 cm
28
smoke
FOR INCLINED OR POINTED ROOFS
For installation to inclined or pointed ceilings, and rooms with an
inclined ceiling, smoke alarms should be installed at least 10 cm
vertically underneath the highest point, and no more than 90 cm
horizontally from the highest point.
These distances also apply when multiple alarms are installed in
one room. Install individual smoke alarms at appropriate distances
from each other.
CEILING INSTALLATION
When fitting smoke alarms to the ceiling, keep a distance of at
least 50 cm from a wall.
ANGLED CEILING
In rooms having a ceiling at an angle greater than 7 degrees
(corresponds to a height difference of about 50 cm over 4 m),
smoke alarms should be positioned on the ceiling in the higher
part of the room.