Honeywell SONIK Guia De Inicio Rapido página 6

Tabla de contenido

Publicidad

Installation
CAUTION
1. Check that Se
archzone Sonik unit has not been damaged during transport.
2. Check that the working environment (temperature) is within the range.
3. Do NOT open the front enclosure.
4. Do NOT modify the front enclosure or component parts as this will compromise the HAZLOC certification.
5. Open and close the end cap with care to avoid deformation.
6. Installation, set-up and maintenance must be conducted only by trained and authorized personnel. Refer
to Technical Manual at all times.
7. Secure the unit in position when untightening the bracket bolts. Accidental release can cause injury.
8. Check the mating surfaces prior to assembly (threads, o-rings). Ensure that they are clean and free of
contaminants.
9. Check the o-rings prior to assembly, replace if damaged.
10. Searchzone Sonik is supplied without cable glands. Ensure that all cable entry threads are sealed with
an appropriate plug to eliminate water ingress and thread damage. At installation, all cable entry plugs
are to be removed and replaced with appropriate cable glands or blanking plugs to meet local HAZLOC
.
requirements
Searchzone Sonik will normally be mounted at height, typically on a pole using supplied U-bolts and
covering the area to be protected. The supplied Standard Adjustable Mounting Bracket
allows mounting on a plate, pole or other plant infrastructure. All bolts are retained to avoid loss during
installation.
Searchzone Sonik has two cable entries for easy wiring with either M25 or 3/4" NPT options. Wires
are terminated at the terminal connectors as per the wiring diagram. Spare wires must be suitably
terminated. Wiring must be in accordance with local, national and company regulations.
Exposed or bare wires must be avoided.
Refer to Technical Manual for instructions on mechanical and electrical installation. You can download
the Technical Manual from www.honeywellanalytics.com
Commissioning
CAUTION
1. A mobile device with Searchzone Sonik Mobile App installed is a prerequisite for detector settings
adjustment made via the Bluetooth connection.
2. Commissioning or proof test of Searchzone Sonik is not complete until the unit is tested to verify
that it functions according to its specifications.
1. Check that Searchzone Sonik unit is mounted and wired correctly. Refer to Installation section of
Technical Manual for instructions.
2. Connect to Searchzone Sonik Mobile App via Bluetooth. Refer to Mobile App section of Technical
Manual for instructions.
3. Check that Searchzone Sonik settings are configured as recommended by the relevant site survey
document.
4. If necessary, adjust detector settings. Refer to Mobile App section of Technical Manual for
instructions.
5. Check that Searchzone Sonik safety outputs are working properly. Refer to Maintenance section of
Technical Manual for instructions.
You can download the Technical Manual from www.honeywellanalytics.com
6

Publicidad

Tabla de contenido
loading

Tabla de contenido