The values or options in the screen displays shown must be entered before start-up.
TABLE 3.
CONTROL
LIMITS
SUCTION PRESSURE ON/OFF
SETPOINT #1
SETPOINT #2
SUCTION TEMPERATURE ON/OFF (1)
SETPOINT #1
SETPOINT #2
SUCT PR CAP INCREASE
SETPOINT #1
SETPOINT #2
SUCT TEMP CAP INCREASE (1)
SETPOINT #1
SETPOINT #2
SUCT PR CAP DECREASE
SETPOINT #1
SETPOINT #2
SUCT TEMP CAP DECREASE
SETPOINT #1
SETPOINT #2
HIGH DSCH PRESS UNLD
SETPOINT #1
SETPOINT #2
LIQ INJECTION SOLENOID CONTROL TEMP
VIA:
OIL INJECTION TEMPERATURE
OIL SEPARATOR TEMPERATURE
OILPMP RESTART (D/S)
OIL SEPARATOR HEATER
CAP CTRL °F ON/OFF
SETPOINT #1
SETPOINT #2
CAP CTRL °F INCR
SETPOINT #1
SETPOINT #2
CAP CTRL °F DECR
SETPOINT #1
SETPOINT #2
LAG, CAPACITY STEP
VOL SLIDE ADJ FACTOR
MINIMUM RUN CAPACITY
LEAD, MAXIMUM CAP FLAG
ECONOMIZER SOLENOID
VOL ADJ CAP RANGE
VISSION MICRO-CONTROLLER
MANUAL DE OPERACIONES
SYSTEM CONTROL LIMIT VALUES WORKSHEET
SYSTEM VALUES
CUT IN
(1)
(1)
(1)
(1)
(1)
(2)
(2)
(2)
(3)
(3)
- 49 -
VALUE LIMITS
CUT OUT
CUT IN
30"/150
30"/150
30"/150
30"/150
30"/150
30"/150
0/300
0/300
ON
200°F
200°F
1.0/8.0
80/130
-99/200
-99/200
-99/300
-99/300
-99/200
-99/200
0/100
-100/100
10% / 90%
50/100
0% / 100%
0/100
DEFAULT VALUES
CUT OUT
CUT IN
CUT OUT
30"/150
10
30"/150
15
20°F
25°F
30"/150
20
30"/150
25
28°F
33°F
30"/150
18
30"/150
23
24°F
29°F
0300
200
0/300
210
OFF
ON
50°F
120°F
105°F
50°F
120°F
105°F
1.0/8.0
2.8
80/130
95
-99/200
20
-99/200
25
-99/300
28
-99/300
33
-99/200
24
-99/200
29
- - -
10
- - -
0%
- - -
30
50/100
95
0% /
80%
75%`
100%
- - -
100%
100%
Cont'd on next page
ORIGINAL ISSUE
6
11
10°F
15°F
20
25
27°F
32°F
18
23
25°F
30°F
190
200
OFF
3.0
105
10
15
27
32
25
30
- - -
- - -
35%
90
3/03