Descargar Imprimir esta página
System Sensor 1151E Instrucciones De Instalación Y Mantenimiento

System Sensor 1151E Instrucciones De Instalación Y Mantenimiento

Publicidad

Idiomas disponibles

Idiomas disponibles

Enlaces rápidos

INSTALLATION AND MAINTENANCE INSTRUCTIONS FOR MODEL 1151E
LOW PROFILE IONISATION SMOKE DETECTOR
Before installing detectors, please thoroughly read System Sensor's Manual I56-407-XX, Guide for the Proper Use of System Smoke Detectors
which provides detailed information on detector spacing, placement, zoning, wiring, and special applications. Copies of this manual are available
at no charge from System Sensor.
GENERAL DESCRIPTION
Model 1151E ionisation detectors use state-of-the-art sensing chambers. These detectors are designed to provide open area protection and to be
used with compatible control panels only. The ability to plug these detectors into a variety of base options extends panel compatibility and
application flexibility.
Two LEDs on each detector light to provide a local 360° visible alarm indication. Remote LED annunciator capability is available as an optional
accessory wired to the standard base terminals. These detectors also have a latching alarm feature. The alarm can be reset only by a momentary
power interruption. These detectors may be tested by activating an internal reed switch with a magnet.
SPECIFICATIONS
Size:
Cover Height:
43 mm
Cover Diameter:
102 mm
Weight:
102 g
Operating Temperature Range:
-10°C to 60°C
Note: Do not install in locations where the normal ambient temperature range extends beyond 0°C to 50°C for extended periods
Operating Humidity Range:
10% to 93% Relative Humidity, Non-condensing
Latching Alarm:
Reset by momentary power interruption.
This detector has been independently tested and certified to EN54 part 7.
COVERAGE
As a general guide, the 1151E smoke detector should provide adequate protection of an area 70-90m², where the ceiling is smooth and there is no
significant air movement. Where installation conditions or response requirements vary, different spacing may be necessary. It is essential to
consult local codes of practice for the installation of fire alarm systems before installing smoke detectors.
BASE SELECTION AND WIRING GUIDE
Refer to the installation instructions supplied with the plug-in detector bases for wiring details. System Sensor has a variety of detector bases
available for this smoke detector, including standard 2-wire with or without current limiting resistors, Schottky diode or changeover relay.
All bases are provided with screw terminals for power and remote indicator connections and relay contact connections, if applicable. The
electrical ratings for each detector-base combination are also included in the base installation instructions.
NOTE:
All wiring must conform to applicable local and national codes and regulations.
NOTE:
Verify that all detector bases are installed, that the detector monitoring circuits have been tested and that the wiring is correct. (Refer to
detector base instructions for testing procedure)
Remove power from detector monitoring circuits before installing detectors.
INSTALLATION
1.
Place the detector into the detector base.
2.
Rotate the detector clockwise with gentle pressure until the detector drops into place.
3.
Continue rotating the detector clockwise to lock it in place.
4.
After all detectors have been installed, apply power to the detector monitoring circuits.
5.
Test the detector as described under TESTING.
6.
Reset the detector at the system control panel.
7.
Notify the proper authorities that the system is in operation.
Tamper-Resistance
The detector bases include a feature that, when activated, prevents removal of the detector without the use of a tool. See the installation
instructions for the detector base for details of how to use this feature.
Dust covers are fitted to the detectors to help protect units during shipment and when first installed. They are not intended to
provide complete protection against contamination; therefore detectors should be removed before beginning construction, major
re-decoration or other dust producing activity. Dust covers must be removed before the system can be made operational.
D100-62-00
WARNING
CAUTION
Figure 1. Test Magnet Positioning.
TESTING
Detectors must be tested after installation and following periodic maintenance.
However, before testing, notify the proper authorities that the smoke detector system
is undergoing maintenance and the system will be temporarily out of service.
Disable the zone or system undergoing maintenance to prevent unwanted alarms.
Test the detector as follows:
Test Magnet (Model M02-24 - optional)
1.
Test the detector by positioning the test magnet against the detector body approximately 2cm from LED1 in the direction of the metering
socket (see Figure 1).
2.
Both LEDs should latch on within 30 seconds, indicating an alarm and activating the panel.
Calibrated Sensitivity Test (MOD400R)
1.
Use the MOD400R Test Module with a digital or analogue voltmeter to check detector sensitivity as described in the test module manual.
After completion of all tests notify the proper authorities that the system is operational.
Detectors that fail these tests should be cleaned as described under MAINTENANCE and re-tested. If the detectors still fail these tests they
should be returned for repair.
MAINTENANCE
Before cleaning, notify the proper authorities that the system is undergoing maintenance and will be temporarily out of service. Disable the
system to prevent unwanted alarms.
1.
Remove the detector to be cleaned from the system.
2.
Remove the detector cover (Note: Regulations in some countries may prohibit this operation on ionisation type sensors). Use a small flat
blade screwdriver to gently release each of the four cover removal tabs that hold the cover in place. (See Figure 2)
3.
Vacuum the outside of the screen carefully without removing it.
4.
Remove the sensor screen. Pull the screen straight away from the sensing chamber until it snaps out of place. Replacement screens are
available.
5.
Use a vacuum cleaner and/or clean, compressed air to remove dust and debris from the sensing chamber.
6.
Reinstall or replace the sensing chamber screen by sliding the edge without the tabs over the sensing chamber. Make sure that one of the
screen contacts engages with the PC board contact.
7.
Reinstall the detector cover. Use the test module socket and LEDs to align the cover with the sensor assembly. Snap the cover into place
making sure all tabs are engaged.
8.
When all sensors have been cleaned, restore power to the system and test the sensor(s) as described in the TESTING section of this
manual.
LIMITATIONS OF SMOKE DETECTORS
This smoke detector is designed to activate and initiate emergency action but will do so only when used in conjunction with other equipment.
Smoke detectors will not work without power.
Smoke detectors will not sense fires which start where smoke does not reach the detectors. Smoke from fires in chimneys, in walls, on
roofs, or on the other side of closed doors may not reach the smoke detector and trigger the unit.
A detector may not detect a fire developing on another level of a building. For this reason, detectors should be located on every level of a
building.
Smoke detectors also have sensing limitations. Ionisation detectors offer broad range fire-sensing capability but they are better at detecting
fast, flaming fires than slow, smouldering fires. Photo-electronic detectors sense smouldering fires better than flaming fires. Because fires
develop in different ways and are often unpredictable in their growth, neither type of detector is necessarily better and a given detector may not
always provide warning of a fire. In general, detectors can not be expected to provide warnings for fires resulting from inadequate fire protection
practices, violent explosions, escaping gas, improper storage of flammable liquids like cleaning solvents, other safety hazards, or arson. Smoke
detectors used in high air velocity conditions may fail to alarm due to dilution of smoke densities created by such frequent and rapid air
exchanges. Additionally, high air velocity environments may create increased dust contamination, demanding more frequent maintenance.
Smoke detectors cannot last forever. Smoke detectors contain electronic parts. Even though detectors are made to last over 10 years, any of
these parts could fail at any time. Therefore, test your smoke detector system at least semi-annually. Clean and take care of your smoke
detectors regularly. Taking care of the fire detection system you have installed will significantly reduce your liability risks.
1
Pittway Tecnologica S.p.A, Via Caboto 19/3, 34147 Trieste, Italy
Figure 2. Sensor with Cover Removed
WARNING
© System Sensor 2000
I56-0778-003

Publicidad

loading

Resumen de contenidos para System Sensor 1151E

  • Página 1 Detectors that fail these tests should be cleaned as described under MAINTENANCE and re-tested. If the detectors still fail these tests they As a general guide, the 1151E smoke detector should provide adequate protection of an area 70-90m², where the ceiling is smooth and there is no should be returned for repair.
  • Página 2 STAMPATO DESCRIZIONE GENERALE I sensori a camera di ionizzazione modello 1151E utilizzano lo stato dell’arte nel campo delle camere di ionizzazione. Tali sensori sono progettati TEST per la protezione di aree aperte e per venire utilizzati esclusivamente con pannelli di controllo compatibili. La possibilità di abbinare questi sensori ad una varietà...
  • Página 3 MANTENIMIENTO Como norma general, el detector de humo 1151E debería ofrecer la protección adecuada de una zona de 70-90m² en donde el techo sea liso y no exista movimiento de aire notable. Cuando varíen las condiciones de instalación o los requisitos de respuesta, puede que sea necesario modificar Antes de limpiar los detectores, notifique a las autoridades competentes que el sistema está...
  • Página 4 FLACHEN IONISATIONS-RAUCHMELDER 1151E ALLGEMEINE BESCHREIBUNG Das Model 1151E verwendet eine Meßkammer nach dem Ionisationsprinzip. Die Rauchmelder sind nur für die dafür vorgesehenen Brandmelderzentrale einzusetzen. Diese Melder können in eine Vielzahl von unterschiedlichen Montage-Sockeln eingebaut werden. Abbildung 1. Positionieren des Testmagneten Zwei LEDs an jedem Melder ermöglichen eine 360°-Alarmanzeige am Melder.