Setting The Ventilation; Kitchen Flow Control; Adjustment Of Other Wet Rooms - S&P VMC AKOR ST HR Manual De Instrucciones

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Fresh air output
Plenum
4 nozzles
Air output nozzles
Plenum
8 nozzles
Air output nozzles
IMPORTANT TIP: Insulate the network with a layer of glass wool (70 mm) to improve network insulation and
insulate the dual flow unit similarly.

4. SETTING THE VENTILATION

4.1 Kitchen flow control

The kitchen vent is connected to the Ø125mm nozzle of the
extraction plate.
Type of housing
T2/3
T4
T5 y +

4.2 Adjustment of other wet rooms

Wet room vents are connected to the Ø80 mm nozzles on the face extraction
According to the housing regulations, flows are:
Room(s) with bath or shower
Single WC
Multiple WC
Other wet rooms: laundry...
ENGLISH
OR
Setting the kitchen flap lever
Position 3
Position 4
Position 5/+
T3 to T7 housing
30 m³/h
30 m³/h
15 m³/h
15 m³/h
Exhaust Plenum
5 nozzles
i l d d
OR
Extraction nozzles
Exhaust air
Regulator set at 15 m
17 / 40
Air outlet
Exchanger
Air intake
Fresh air
3
/h
Regulator set at 30 m
NT_51895501_AKOR ST HR-AN_140325.docx
3
/h