Vent Safety Shutoff System; Proper Main Burner Flame; Proper Pilot Flame - Empire GWT-25W-2 Instrucciones De Instalación Y Manual Del Propietario

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

This appliance must be properly connected to a venting system.
This appliance is equipped with a vent safety shutoff system.
Warning: Operation of this wall furnace when not connected
to a properly installed and maintained venting system or
tampering with the vent safety shutoff system can result in
carbon monoxide (CO) poisoning and possible death.
This furnace is equipped with a manual reset vent safety switch.
The manual reset vent safety switch will cause gas flow to the main
burner to "shut off" due to improper venting or a blocked flue.
To reset the manual reset vent safety switch:
1.
Remove outer casing.
2.
Depress manual reset button. The manual reset vent safety
switch is located on the draft diverter.
3.
Replace outer casing.
If the manual reset vent safety switch continues to "shut off" the gas
flow to the main burner a qualified service person must be contacted
to inspect for improper venting, blockage in the vent pipe or the
manual reset vent safety switch for being defective.
The correct flame will be a short blue inner flame with a much larger
light blue outer flame. The burner does not have a primary air
adjustment. The flame will be proper if the factory-set pressure and
orifice are used. After the furnace has begun operating, cleaning
of the burner may be needed for proper flame, examine at least 2
times per season.
To clean burner ports, disconnect the gas supply to the valve. Remove
the burner assembly from the combustion chamber. Remove pilot
burner from main burner and then remove the main burner. Force
water into the ports and blow dry with vacuum cleaner air, or low
pressure compressed air.
The correct flame will be blue, extending past the thermopile. The
flame will surround the thermopile just below its tip.
Natural gas pilots require adjusting when the inlet gas pressure is
above 5" w.c. (1.245kPa). Remove the pilot cover screw on the
control valve and turn the adjustment screw clockwise to reduce
flame. Replace pilot cover screw to eliminate gas leaking at that
control valve opening.
LP gas (propane) will not require adjustment.
After use, cleaning may be required for the proper flame.
Examine the pilot flame before and during each heating season.
37409-0-0616

VENT SAFETY SHUTOFF SYSTEM

PROPER MAIN BURNER FLAME

PROPER PILOT FLAME

WIReS FOR
ON/OFF DeVICe
Figure 8
Figure 9
Figure 10
Page 13

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Gwt-35w-2

Tabla de contenido