10.26 Inputs
Configure inputs.
Assigned inputs to process values.
Steam inputs
A.P
input 2 for the steam pressure sensor, range 4-20 mA input, or may be configured
D
for temperature sensor.
A.Dp
input 1 ILVA steam flowmeter, range 4-20 mA input.
D
Feedwater inputs
B.q
input 3 for the feedwater ELM flowmeter, range 4-20 mA input.
W
v
B.p
input 2 taken from the Steam Output is used to give a pressure figure for the
W
feedwater input.
B.T
input 7 for the feedwater temperature, set
W
Pt100 parameters.
Condensate Return inputs
C. q
input 4 for the condensate return ELM a
W
v
flowmeter, range 4-20 mA input.
C.T
input 8 for the condensate return temperature,
W
set Pt100 parameters.
GAS Flow inputs
X.Qv
input 5 for GAS MTL10
4-20 mA input.
Blowdown
Y.Vb
input 11 for BBD valve input, set its ranges.
Y.Vt
input 10 for TDS valve input, set its ranges.
IM-P408-04 AB Issue 2
Select input parameters
flowmeter, range
27