LEGRAND Wattstopper BZ-50 Manual De Instructions
Ocultar thumbs Ver también para Wattstopper BZ-50:

Publicidad

Idiomas disponibles

Idiomas disponibles

Enlaces rápidos

No: 24566 – 08/16 rev. 1
Catalog Numbers • Les Numéros de Catalogue • Números de Catálogo: BZ-50/BZ-50RC
Country of Origin: Made in China • Pays d'origine: Fabriqué en Chine • País de origen: Hecho en China
BZ-50-U is BAA and TAA compliant (Product produced in the U.S.)
BZ-50
The BZ-50 and BZ-50RC power packs are the foundation for any low voltage lighting control system. The BZ-50 and BZ-50RC supply
low voltage power to occupancy sensors and other control devices, switching line voltage in response to signals from control devices.
The power pack is attached to existing junction boxes or mounted into fixture wiring trays.
High voltage connections should use at least 14-gauge. For the BZ-50, low voltage wiring should use at least 22-gauge wire. The
BZ-50RC supplies low voltage power via shielded RJ45 cable. Always check local building codes. After initial wiring is complete,
check wiring diagram to verify power pack is wired correctly. Improper wiring can cause damage to power pack, lighting system, and
occupancy sensor.
Line
Voltage
1. Make sure power has been turned off at the circuit breaker.
2. Connect wires as shown in in the following diagrams, depending
on the model and application.
At least three sensors can be powered by the power pack.
Installation Notes
1. Power packs should be installed in accordance with state, local and national electrical codes and requirements.
2. Power packs are designed to attach to existing or new electrical enclosures with 1/2 inch knockouts.
3. For the BZ-50, most applications require UL listed, 18-22 AWG, 3-conductor, Class 2 cable for low voltage wiring. For plenum
return ceilings, use UL listed plenum-approved cables.
For the BZ-50RC, connect an FS-C1 or FS-C3 cable between the RJ45 jack-equipped sensor and the BZ-50RC, as appropriate
for the distance between the sensor and power pack. Other cable accessories are shown in the Ordering information section.
NOTE: The BZ-50RC can connect to a sensor with standard wiring terminals by using an FS-C2 cable.
4. The BZ-50 BZ-50RC are Class 2 Output Power Supplies, suitable for parallel interconnection of up to 10 units maximum. These
powerpacks are UL Listed for Interconnection of Power Sources in accordance with the National Electric Code.
5. Refer to occupancy sensor data sheet to determine maximum number of sensors. Power pack mA output is 225mA.
BZ-50RC
DESCRIPTION
INSTALLATION AND WIRING
Low Voltage
Class 2
BZ-50
Wattstopper
Power Pack
Bloc d'alimentation
Fuente de alimentación
Installation Instructions • Instructions d'Installation • Instrucciones de Instalación
Voltages ..........................................120–277VAC,50/60Hz
Load Requirments
Ballast .................................. 20amp @120–277VAC
Incandescent ................................ 20amp @120VAC
Motor ......................................... 1HP @120/240VAC
Output .................225mA @24VDC (with relay connected)
Low Voltage Input
Control ON ...............................................12-24VDC
Operating Temperature .......................32°-104°F (0-40°C)
Line
Voltage
WARNING: TURN THE POWER OFF AT THE
CIRCUIT BREAKER BEFORE WIRING.
®
SPECIFICATIONS
Low Voltage cable
with RJ45 connector
BZ-50RC

Publicidad

Tabla de contenido
loading

Resumen de contenidos para LEGRAND Wattstopper BZ-50

  • Página 1 Wattstopper ® Power Pack Bloc d’alimentation Fuente de alimentación No: 24566 – 08/16 rev. 1 Installation Instructions • Instructions d’Installation • Instrucciones de Instalación Catalog Numbers • Les Numéros de Catalogue • Números de Catálogo: BZ-50/BZ-50RC Country of Origin: Made in China • Pays d’origine: Fabriqué en Chine • País de origen: Hecho en China BZ-50-U is BAA and TAA compliant (Product produced in the U.S.) SPECIFICATIONS Voltages ..........120–277VAC,50/60Hz...
  • Página 2: Over Current Protection

    BZ-50 Parallel interconnect for multiple BZ-50 Single load control load control from a single sensor Optional Optional Local Local Switch Switch Neutral White White Neutral BZ-50 BZ-50 120VAC Black Line 120VAC Black Line Power Pack Power Pack 277VAC 277VAC Fixture Fixture Class 2 Low Voltage...
  • Página 3: Ordering Information

    ORDERING INFORMATION Catalog No Description BZ-50 Power Pack: 120/277VAC, 50/60Hz, 20A ballast or incandescent BZ-50RC Power Pack: 120/277VAC, 50/60Hz, 20A ballast or incandescent with RJ-45 low voltage output BZ-50RC Accessories FS-C1 One 10’ cable with a shielded RJ45 male connector at each end 10' (3m) FS-C2 One 6”...
  • Página 4: Protection Contre La Surtension

    3. Pour le BZ-50, dans le cas d'un câblage à faible tension, la plupart des applications nécessitent des câbles de classe 2 à trois conducteurs, 18-22 AWG, certifiés UL. Dans le cas de faux-plafonds plénum, utiliser des câbles certifiés UL de type plénum. Pour le BZ-50RC, connectez un câble FS-C1 ou FS-C3 entre le détecteur à...
  • Página 5 Voyant DEL : Le voyant DEL du BZ-50 indique les états suivants : • DEL ÉTEINTE: BZ-50 non alimenté ou présente un court-circuit au niveau de la sortie +24 VCC. • DEL ALLUMÉE et clignotant toutes les 5 secondes: le relais est fermé (charge ACTIVÉE). •...
  • Página 6: Descripción

    INSTRUCCIONES EN ESPAÑOL DESCRIPCIÓN ESPECIFICACIONES Las fuentes de alimentación BZ-50 y BZ-50RC componen la base Voltajes ..........120–277 V CA,50/60 Hz de cualquier sistema de control de iluminación de bajo voltaje. Los Requisitos de carga BZ-50 y BZ-50RC suministran alimentación de bajo voltaje a los Balasto .........
  • Página 7: Funcionamiento

    Interconexión paralela de BZ-50 para el control Control de carga individual de BZ-50 de varias cargas desde un solo sensor Interruptor Interruptor de Apagado de Apagado Local Opcional Local Opcional Neutro Blanco Rojo BZ-50 Neutro Blanco Rojo BZ-50 Línea 120VCA Negro Rojo Fuente de alimentación...
  • Página 8: Información Para Hacer Pedidos

    No. 24566 – 08/16 rev. 1 © Copyright 2016 Legrand All Rights Reserved. 800.879.8585 © Copyright 2016 Tous droits réservés Legrand. www.legrand.us/wattstopper © Copyright 2016 Legrand Todos los derechos reservados.

Este manual también es adecuado para:

Wattstopper bz-50rc

Tabla de contenido