UNIT DESCRIPTION
The CI-200 is a 24VDC Passive Infrared (PIR) occupancy sensor
which controls lighting or HVAC systems based on occupancy and/
or ambient light levels in a given area.
PIR sensing systems are passive systems which react to changes
in infrared energy (moving body heat) within the coverage area. PIR
sensors must directly "see" motion of an occupant to detect them,
so careful consideration must be given to sensor placement.
COVERAGE PATTERNS
The CI-200 has a multi-cell, multi-tier Fresnel lens with a field of view
of 360°. The sensor has two lens pattern options. The Extended Range
Lens will cover up to 1200 sq ft when mounted from 8-12 ft. The High
Density/Reduced Range Lens will cover up to 500 sq ft when mounted
at 8-12ft.
Coverage shown in the diagrams below is maximum and represents
coverage for half-step walking motion, with no barriers or obstacles
Extended Range Lens
(Standard) CI-200
Side View
8 ft
2,4m
Typical desk-top level
Niveau supérieure de bureau typique
Nivel de sobremesa típico
22 ft
6,7 m
PLACEMENT
The effective coverage distances may be slightly less than the maximum sensing distance (see Coverage Patterns), depending upon
obstacles such as furniture or partitions, and this must be considered when planning the number of sensors and their positioning. See
the list below for approximate coverage distances for different types of motion.
Approximate coverage, for a mounting height of 8 feet:
Lens option
Walking motion
Extended Range
up to 22ft radius (1200 sq ft)
High Density
up to 12ft radius (500 sq ft)
The CI-200 sensor can be mounted at various heights. When you will be mounting at heights
other than 12 ft, be aware that as you decrease the mounting height, you will decrease the range
and increase the sensitivity to smaller motions. Conversely, when you increase the height, you will
increase the range and decrease the sensitivity to smaller motions. At heights of more than 12 -14
ft, you may start to significantly reduce sensitivity.
Often the best location to install a CI-200 in a closed office is off-center. Avoid placing a sensor
directly in line with an open door in which it has a clear view out, as the sensor may detect people
walking by.
360° Passive Infrared • Low Voltage Occupancy Sensor
Pasivo infrarrojo de 360° • Voltaje bajo Sensor de ocupación
Top View @ 8ft
44 ft
13,41 m
13 ft
7 ft
3 ft
0 3 ft
7 ft
13 ft
4m
2,1m
1m
1m
2,1m
4m
Workstation (hand motion)
12ft radius (500 sq ft)
9ft radius (300 sq ft)
IRP 360 ° • Détecteur de présence de basse tension
SPECIFICATIONS
Voltage Supply .........................20–30VDC (24VDC Typical)
Current Consumption ...............@24VDC, 24mA Maximum
Isolated Relay Rating ....................... 1A @24VDC or 24VAC
Operating Temperature.............. 32° to 131°F (0° to 55°C)
Time Delay Adjustment ................ 15 seconds–30 minutes
PIR Coverage
Model CI-200 ...................................... up to 1200ft2
Model CI-200-1 .................................... up to 500ft2
Light Level Adjustment ........................................ 1–190FC
Sensitivity Adjustment ...................... Minimum-Maximum
UL & CUL Listed
High Density/Reduced
Range Lens CI-200-1
Side View
Typical desk-top level
Niveau supérieure de bureau typique
Nivel de sobremesa típico
22 ft
6,7 m
CI-200
Top View @ 8ft
8 ft
2,4m
12 ft
9 ft
7 ft
5 ft
3 ft
0
3 ft
3,7m
2,7m
2,1m
1,5m
1m
1m
1,5m
18'
Sensor
version 2
24 ft
7.32 m
5 ft
7 ft
9 ft
12 ft
2,1m
2,7m
3,7m
12'