INSTALLATION AND MAINTENANCE INSTRUCTIONS
SC-6
Six Supervised Control Module
SPECIFICATIONS
Normal Operating Voltage:
Stand-By Current:
Alarm Current:
Temperature Range:
Humidity:
Dimensions:
Accessories:
Wire Gauge:
Maximum Monitored Output Circuit
Wiring Resistance:
RELAY CONTACT RATINGS:
CURRENT RATING
2 A
3 A
2 A
0.46 A
0.7 A
0.9 A
0.5 A
0.3 A
BEFORE INSTALLING
This information is included as a quick reference installation guide. Refer to
the appropriate control panel installation manual for detailed system infor-
mation. If the modules will be installed in an existing operational system,
inform the operator and local authority that the system will be temporarily
out of service. Disconnect the power to the control panel before installing the
modules. This system contains static sensitive components. Always ground
yourself with a proper wrist strap before handling any circuits so that static
charges are removed from the body. The housing cabinet should be metallic
and suitably grounded.
NOTICE: This manual should be left with the owner/user of this equipment. This
manual refers only to installations conforming to EN54 requirements, for UL
installations please refer to I56-1802 (former number D500-50-00).
GENERAL DESCRIPTION
The SC-6 Six Supervised Control Module is intended for use in an intelligent
alarm system. Each module is intended for switching applications involving
DC which require wiring supervision. A common SLC input is used for all
modules. Each module has its own address. A pair of rotary code switches is
used to set the address of the first module from 01 to 94. The remaining mod-
ules are automatically assigned to the next five higher addresses. Provisions
are included for disabling a maximum of three unused modules to release the
addresses to be used elsewhere. Each module also has panel controlled green
LED indicators. The panel can cause the LEDs to blink, latch on, or latch off.
Each module has terminals for connection to an external supply circuit for
powering devices on its Monitored Output Circuit.
Each supply must be power limited and its voltage/current limits must be at
or below those specified in Table 1.
There is a short circuit protection monitor for each module. This is provided
to protect the external power supply against short circuit conditions on the
Monitored Output Circuit.
15-32VDC
2.65 mA @ 24V
35 mA (assumes all six relays have been switched once and all six LEDs solid on)
-10°C to 55°C
10 to 93% Non condensing
17.3cm H x 14.7cm W x 3.2cm D
Suitably grounded metallic cabinet
0.8mm² - 3.25mm²
40 Ohms
MAXIMUM VOLTAGE
25 VAC
30 VDC
30 VDC
30 VDC
70.7 VAC
125 VDC
125 VAC
125 VAC
LOAD DESCRIPTION
PF = 0.35
Resistive
Resistive
(L/R = 20ms)
PF = 0.35
Resistive
PF = 0.75
PF = 0.35
COMPATIBILITY REQUIREMENTS
To ensure proper operation, this module shall be connected to a listed compat-
ible control panel.
The SC-6 Module shall be mounted in a suitably grounded Metallic Cabinet
for EMC compliance.
NOTE: Three shunts on Sync Generator MUST NOT be removed.
INCLUDED:
Shipped on Board:
(1) Small shunt
(6) Large shunts on Enable Power Supply Monitors
(6) Large shunts on Disable Short Circuit Protection
(3) Large shunts on Sync Generator
(4) MACHINE SCREWS
(2) SMALL
(15) LARGE
SHUNTS
SHUNTS
(2) NUTS
(1) LONG POWER SUPPLY JUMPER
1
Honeywell Products and Solutions Sàrl
Zone d'Activités La Pièce 16
CH-1180 ROLLE, Switzerland
APPLICATION
Non-coded
Non-coded
Coded
Non-coded
Non-coded
Non-coded
Non-coded
Non-coded
(7) 1 × 4
TERMINAL
BLOCKS
(7) 1¼˝ (32mm) STANDOFFS
(2) EOL RELAY
CONNECTOR
ASSEMBLES
(5) SHORT POWER
SUPPLY JUMPERS
(6) 47K OHM
END OF LINE
RESISTORS
C0958-00
I56-2253-009
3/2/2020