en | Specifications
6
Specifications
These ratings apply to alarm and standby conditions.
NOTICE!
For the proper calculation of the total current consumption, you have to add both the general
current consumption of the head and of the isolator base, if used in the circuit.
Operating voltage (SLC loop)
Maximum current consumption detector head at
77 °F (25 °C) and 39 V bus voltage
–
Standby
–
Alarm
–
When polled
Maximum allowable line resistance
Maximum airflow
Maximum current consumption isolator base at
77 °F (25 °C) and 39 V bus voltage
–
Standby
–
Triggered
Sensitivity
–
Smoke sensor
–
Heat sensor (FAP-440 detectors)
–
Heat sensor (FAH-440 heat detectors)
Installation temperature
Storage temperature
–
Without CO sensor
–
With CO sensor
Humidity
Protection category
Mounting locations and heights in general
Maximum spacing between detectors
–
Smoke detector
–
Heat detector
Minimum mounting distance to magnets
(e.g. loudspeaker)
Maximum wiring length to C point
Dimensions (diameter x height)
–
Detector
–
Detector with 4-inch base
–
Detector with 6-inch base
Housing material
Table 6.1 Technical Specifications
F.01U.123.589 | 5.0 | 2012.02
24 V DC to 41 V DC
170 μA
5 mA
22 mA ± 20%
50 Ω
4000 ft/min (20m/s)
70 μA
10 mA
1.25%/ft to 3.5%/ft
+135 °F (+57 °C) + RoR
+135 °F to +194 °F (+57 °C to +90 °C), programmable +RoR
+32 °F to +100 °F (0 °C to +38 °C)
If the sensitivity temperature is programmed within a range
of +175 °F to +249 °F (+79.4 °C to +120.6 °C), the maximum
installation temperature is 150 °F (+66 °C).
-13 °F to +176 °F (-25 °C to +80 °C)
+14 °F to +122 °F (-10 °C to +50 °C)
< 95% (non-condensing)
IP 42
Refer to NFPA-72
30 ft.
50 ft.
11.8 in. (30 cm)
9.8 ft. (3 m)
4.4 in. x 2.0 in. (11.2 cm x 5.1 cm)
5.0 in. x 2.5 in. (12.7 cm x 6.4 cm)
7.0 in. x 2.5 in. (17.8 cm x 6.4 cm)
Cycoloy/ABS
Installation Guide
Analog Detectors and Bases
Bosch Security Systems, Inc.