Replace The Remote Controller Cover
Replace the existing Remote controller cover with Remote controller
cover 5 to close the hole left after remove the Remote controller.
1. Release the Remote controller cover's hooks from behind the
Front Plate e.
e
Front Plate
Existing Remote
controller cover
2. Press from front to fi x the Remote controller cover 5 on the front
plate.
e
Front Plate
Remote
controller
cover
5
TEST RUN
8
1. Before test run, make sure below items have been checked:-
a) Pipework are properly done.
b) Electric cable connecting work are properly done.
c) Tank Unit is fi lled up with water and trapped air is released.
d) Please turn on the power supply after fi lling the tank until full.
e) In order to check whether the tank is full, switch heater once
for about 10 min.
2. Switch ON the power supply of the Tank Unit. Set the Tank
Unit RCCB /ELCB to "ON" condition. Then, please refer to the
Operation Instruction for operation of Remote Controller 1.
3. For normal operation, Water Pressure Gauge d reading should
be in between 0.05 MPa and 0.3 MPa. If necessary, adjust the
Water Pump 2 SPEED accordingly to obtain normal water
pressure operating range. If adjust Water Pump 2 SPEED
cannot solve the problem, contact your local authorized dealer.
4. After test run, please clean the Water Filter Set 6. Reinstall it
after fi nish cleaning.
CHECK WATER FLOW OF WATER CIRCUIT
Confi rm the maximum water fl ow during main pump operation not
less than 15 l/min.
*Water fl ow can be check through service setup (Pump Max Speed)
[Heating operation at low water temperature with lower water fl ow
may trigger "H75" during defrost process.]
10
Hook (6 places)
Hook (6 places)
RESET OVERLOAD PROTECTOR 9
Overload Protector 9 a serves the safety purpose to prevent the
water over heating. When the Overload Protector 9 a trip at high
water temperature, take below steps to reset it.
1. Take out the cover.
2. Use a test pen to push the centre button gently in order to reset
the Overload Protector 9.
3. Fix the cover to the original fi xing condition.
MAINTENANCE
9
In order to ensure safety and optimal performance of the Tank
Unit, seasonal inspections on the Tank Unit, functional check
of RCCB/ELCB, fi eld wiring and piping have to be carried out
at regular intervals. This maintenance should be carried out by
authorized dealer. Contact dealer for scheduled inspection.
Maintenance for Water Filter Set 6
1. Turn OFF power supply.
2. Set the two valves for the Water Filter Set 6 to "CLOSE".
3. Take off the clip, then gently pull out the mesh. Beware of small
amount water drain out from it.
4. Clean the mesh with warm water to remove all the stain. Use
soft brush if necessary.
5. Reinstall the mesh to the Water Filter Set 6 and set back the
clip on it.
6. Set the two valves for the Water Filter Set 6 to "OPEN".
7. Turn ON power supply.
Maintenance for Safety Relief Valve k
It is strongly recommended to operate the valve by turn the knob
counter clockwise to ensure free water fl ow through discharge
pipe at regular intervals to ensure it is not blocked and to remove
lime deposit.
Use test pen to push
this button for reset
Overload protector 9.