GENERAL DESCRIPTION
The MCP200CS Manual Call Point has been specially designed to
be used with Conventional Fire Alarm Systems and is ideal for inter-
nal installations that require manual activation and inhibition of Fire
Alarms and Fire Extinquishment Systems.
The MCP200CS Manual Call Point is activated by pushing the centre
of the Operating Face (black arrows indicate the exact point), and
reset by means of the special key, it provides also local LED indica-
tion of Alarm status (Red LED Fixed).
ACTIVE STATUS
Once happens any fire, user can push the plastic button of the Man-
ual-Call-Point down (see fig 4) then a warning YELLOW-BOARD
would jump up. When the Yellow-Board shows off, it means the MCP
has been activated. The red LED is also switched on drawing the
alarm current from the conventional zone.
RESET
When the MCP has been settled down, the security manager can
reset the Manual-Call-Point back to its stand-by status by using the
attached KEY (see fig 1); whom can find the key hole on the right-
side of Manual-Call-Point then push the key into and till its end, then
pull it out to complete the RESET action.
KEY'S FUNCTION
The key can also be used to disassembly the main-unit out from its
base. User can find two small square holes at the bottom side of the
Manual-Call-Point, whom can use the key to push the springs of
main-unit out through the holes then can easily to depart the whole
Manual-Call-Point into two parts (see fig 3).
INSTALLATION
1. Please use a standard screw driver to fix the base onto its proper
position, then according to the following description to make the
wires connect to the Manual-Call-Point.
2. Pull the connection wires out through the hole of the base-unit.
3. Connected the wires into the L and C wire-holders (there are each
two holes under both L and C labels for Input or Output). Just push
about 5mm of the wire-lead into the wire-holder then the wire will be
auto locked down.
4. Insert the main unit of Manual Call Point into the base unit and
push it down to fix them together.
The manufacter recommends that customers dispose of their used equipments (panels, detectors, sirens, and other devices)
in an environmentally sound manner. Potential methods include reuse of parts or whole products and recycling of products, components, and/or materials.
In the European Union, this label indicates that this product should NOT be disposed of with household waste.
The manufacter reserves the right to modify the technical specifications of this product without prior notice.
G ENGLISH
Recycling information
Waste Electrical and Electronic Equipment (WEEE) Directive
It should be deposited at an appropriate facility to enable recovery and recycling.
WIRING DIAGRAM
The Module can be connected to the Conventional Zone by means
of a standard two wire connection (See Fig. 2).
In the alarm condition the Manual Call Point LED is turned on, two
resistors in parallel limit the current that flows into the LED and the
resultant limiting resistor is 270 ohm.
The alarm current determined by this resistor value can meet the
ranges of typical fire conventional panels and allows, to discriminate
alarms from MCP's or from fire detectors that have been wired on the
same conventional zone.
If the higher alarm resistance (470 ohm) option is required remove
the internal cover B (fig 5) and cut the resistor C.
The supervision of the conventional zone is achieved by connecting
the End Of Line Resistor, 3.9 kohm for the panels.
ELECTRICAL DETAILS
SPECIFICATIONS
Rating of block terminal
Insulation Withstands Voltage
Insulation Resistance
Dimensions (mm)
Operating Temperature Range
Suitable Electric Wire
IP Rating
Material
VALUE
300V 10A (IEC 380V 16A)
PITCH: 5.08mm
AC 1500 V/min
500Mohm or more
@ DC 500V
98.8 x 96.6 x 39.6
-20°C ~ 50°C
AWG 22~14 (IEC 1.5mm
)
2
Suitable for internal Use
ABS Plastic