4
USE AND MAINTENANCE
4. 1
GAS VALVE (fig. 10)
"GG MP" boilers come equipped standard
with a HONEYWELL VR 4605 C gas valve
(for "8-9" models), VR 4605 CB gas valve
(for "10-11" models) and VR 420 PB gas
valve (for "12" models).
When the boiler is ignited the first time, it is
always recommended to bleed the piping by
using the pressure outlet upstream from
the valve (7 fig. 10 - 9 fig. 2).
4.2
GAS VALVE ADJUSTMENT
Calibration of the operating pressures is
done by CLIMIT in the factory. Consequently
they should not be altered. Only when you
switch to another type of gas (butane or
propane) is it permitted to alter the opera-
ting pressures.
It is essential that this operation be car-
ried out exclusively by authorized techni-
cal staff.
When the working pressures have been
adjusted, reseal the regulators.
When the gas pressures are to be reset,
this must be done following a set order: first
the maximum pressure and then the mini-
mum.
4.2. 1
Nominal pressure
adjustment (fig. 11)
Connect the manometer to the pressure
test point located on the burner manifold,
turn boiler ON, and wait until a steady read-
ing on the manometer is obtained. Compare
this reading with that shown in Table 1. If any
correction is required, use an 8mm spanner
on the high pressure adjuster (1) turning
clockwise to increase, counter-clockwise to
decrease the pressure.
4.2.2
Reduced pressure
adjustment (fig. 11)
Turn the boiler OFF, and remove the plug
from the High - Low Coil. Turn the boiler ON
and wait until a steady reading on the
manometer is obtained. Compare this read-
ing with that shown in Table 1.
If any correction is required, use a 3.5 mm
flat blade screwdriver to rotate the low
adjust screw (2), turning clockwise to
increase and counter-clockwise to decrease
the pressure.
When all adjustments are completed,
replace the plug on the coil, and the cap over
the adjustment screws.
4.4
GAS CONVERSION
To convert to butane gas (G30) or propane
gas (G31), the main nozzles must be repla-
ced with another supplied in the boiler gas
conversion kit, pressure regulator (3...20
mbar) with pressure regulator (4...37
HONEYWELL VR 4605 C - VR 4605 CB
HONEYWELL VR 420 PB
TABLE 1
Methane - G20
Burner max. pressure
mbar
Burner min. pressure
mbar
Butane - G30
Burner max. pressure
mbar
Burner min. pressure
mbar
Propane - G31
Burner max. pressure
mbar
Burner min. pressure
mbar
KEY
1
EV1 coil
3
Pressure regulator 3...20 mbar
4
EV2 coil
5
LPG adaptor
6
Plastic cap
7
Pressure inlet upstream
8
Pressure inlet
downstream
9
EV1- EV2 coil
1
9
2
3
GG MP 8
GG MP 9
GG MP 10
9.3
9. 1
9.3
4.5
4.6
4.7
25.2
25.4
25. 1
12.2
12.3
12.0
32.6
30.2
30.0
16.4
16. 1
15.6
KEY
1
Maximum pressure adjusting nut
2
Minimum pressure adjusting screws
3
Plastic cap
IT
ES
GB
FR
RO
RUS
Fig. 10
GG MP 11
GG MP 12
9.3
9.3
4.7
4.6
25. 1
25.6
12.5
12.6
32.7
34.3
16.6
16.6
Fig. 11
39