Function Test - Danfoss AME 110 NL Manual Del Usuario

Actuadores de control modulante
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 12
Manual override ❺
(for service purposes only)
Do not manually operate the drive if
power is connected!
- Remove cover ❺①
- Press and hold the button (on the
bottom side of the actuator) ❺②
during manual override ❺③
- Replace cover ❺④
- Install actuator on valve ❺⑤
Remark:
A 'click' sound after energising the actuator
indicates that the gear wheel has jumped
into normal position.

Function test

The light emitting diodes (LEDs)
❹① (green - direction indicator),
❹② (red - reset and normal mode
indicator) indicate whether the actuator is
in operation or not, the operating status,
and failures, if any.
Red LED:
• No light
- no operation or no power supply
• Constant light
- normal operation
• Flashing light (1 Hz)
- self-adjusting mode
• Flashing light (~ 3 Hz):
- power supply too low
- initial self-adjusting time too short
due to too short valve strokes
- failure during self calibration
Green LED:
• Spindle extracts (green led diode
blinking once per sec.)
• Spindle retracting (green LED on)
• Actuator reached set-point acc. to Y
signal (LED off).