Descargar Imprimir esta página

SSS Siedle VNG 602-02 Informacion De Producto página 4

Fuente de alimentación de vídeo
Ocultar thumbs Ver también para VNG 602-02:

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 10
English
Application
The video line rectifier VNG 602-...
in a 10-grid switch panel housing is
used for central power supply in 1+n
systems with video. It can addition-
ally be used as a universal voltage
supply.
Electrical voltage
Mounting, installation and servicing
work on electrical devices may only
be performed by a suitably qualified
electrician.
Failure to observe this regulation
could result in the risk of serious
damage to health or fatal injury due
to electric shocks.
• Observe DIN EN 60065!
In a building installation, an all-
pole mains switch with a contact
opening of at least 3 mm must be
provided. The device must not be
exposed to water drops or sprayed
water! Sufficient ventilation must be
ensured. Pay particular attention to
ensure that ventilation slots are not
covered.
• For surface mounting, ensure that
"protection against direct contact"
with active parts is provided. For
details, consult VDE 0100/DIN 57100
part 410.
• When using stranded cores as
cable material, these must be fitted
with wire end ferrules without fail.
• The line rectifier in the 120 V
version may only be operated in
a closed switch cabinet. Covering
solely with the ZAP 10-0 is not suffi-
cient. The 120 V variant may only be
used in conjunction with ITE devices.
(Information Technology Equipment)
4
Scope of supply
VNG 602-... comprising:
• • line rectifier for top hat rail
mounting
• this product information
Mounting in distribution cabinet
1 Clip the line rectifier onto the top
hat rail.
Surface mounting
(only 230 V version)
2 Surface mounting only using
accessory ZAP 10-0. Clip the pro-
vided latches onto the back of the
line rectifier. Mount the device on
the wall.
Installation and commissioning
Installation and commissioning pro-
cedures are described in the system
manual 1+n technology (enclosed
with line rectifier NG 602-...).
Terminal assignment
N,
Power connection
L1
+M,
Voltage 30 V DC
-M
Function LED
LED On
Ready for service
LED Off
Fuse is defective
Servicing
The VNG 602-... has a thermal fuse
on the secondary side. After a short
circuit or overload, check the primary
fuse and disconnect the device from
the mains for 1 minute.
Technical specifications
VNG 602-02
Operating voltage:
230 V AC +/–10 %, 50/60 Hz
Output voltage: 30 V DC
Output current: 1.1 A
Fusing: Si 1 T 200 mA, secondary
side thermal fuse
Protection system: IP 20
Ambient temperature:
0 °C to +40 °C
Horizontal pitch (HP): 10
Dimensions (mm) W x H x D:
180 x 89 x 60
Technical specifications
VNG 602-12 USA
Operating voltage:
120 V AC +/–10 %, 50 Hz
For further technical specifications
see above

Publicidad

loading

Este manual también es adecuado para:

Vng 602-12 usa