Nibe HPAC 45 Manual De Instalación página 17

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Valve position checks
Valve in neutral position
If the valve motors have become loose and the valves
have come out of position, adjust the position of the
valves using a wrench to obtain the right valve setting.
Adjust the valves according to the previous table "heat-
ing" and install the valve motors unpowered, with the
arm set to neutral position (current on, control current
off).
At input control signal the valves rotate 90°.
Caution
When changing the heating/cooling mode,
there is a delay of approximately 60 seconds
before the valves change their positions.
HPAC 45 | GB
17

Publicidad

Tabla de contenido
loading

Tabla de contenido