Turn the equipment by using the ON SWITCH 2.
5.
6.
The following message will appear on the display:
MEGABRAS MD-5060x
7.
The PRESS START message will appear immediately.
8.
In order to make repetitive tests performance easier, when the equipment is
turned on, the test voltage will be the same voltage selected for the last per-
formed test, meanwhile the megohmmeter will be in the 500 V steps voltage
test programming mode (led > flashing). To modify this voltage, use the 7
and 8 keys or the fast selection 3456 keys. For a voltage test fine ad-
justment (in 100 V steps) press the ±100 , key. In this condition, the 7 and
8 keys make it possible to decrease or increase the 100 V steps test voltage
to select 500, 600, 700, . . . 4800, 4900 and 5000 Vc.c. voltages.
9.
To leave the voltage test programming mode just press the activated key
again in order to deactivate it (the associated led will stop flashing). Now, the
voltage selected value will be recorded in the equipment RAM memory for fu-
ture tests.
10. Press START 9 key. The HIGH VOLTAGE E led turns on immediately, indi-
cating that the megohmmeter internal generator is applying voltage to the
element that is being tested. If, during the test, it is necessary to change the
test voltage, item 8 sequence shall be repeated.
11. For a few seconds, the self-scale smart system will search for the most con-
venient range for the value being measured. Meanwhile, the display will show
the message "WAIT..."
19