72
NOTAS
Network Variables
■ Air conditioner, ERV, ERV DX, AWHP input/output
1) On/Off (Air conditioner, ERV, ERV DX, AWHP)
Input
Output
Valid Range
NV
SNVT_switch
2) Operation Mode (Air conditioner, ERV, ERV DX, AWHP)
Input
Output
Valid Range
NV
SNVT_hvac_mode
Function
On/Off input
Using NV
network variable : SNVT_switch, nviOnOff
Operation
On/Off control
Function
On/Off display
Using NV
network variable : SNVT_switch, nvoOnOff
Operation
On/Off monitor
Field
value
state
Function
Operation Mode input
Using NV
network variable : SNVT_hvac_mode, nviHea
Operation
Operation Mode control
Function
Operation Mode display
Using NV
network variable : SNVT_hvac_mode, nvoHeatCool
Operation
Operation Mode monitor
Field
value
state
Operation
not used (set in 0 % usually)
0 = OFF
1 = ON
Operation
not used (set in 0 % usually)
HVAC_AUTO = Auto
HVAC_HEAT = Heat
HVAC_COOL = Cool
HVAC_FAN_ONLY
= FAN (Air conditioner, AWHP)
= Normal (ERV, ERV DX
HVAC_DEHUMID = Dehumid