XV/XVI/XV-F SS Vertical Multi-stages Centrifugal Pumps
5.1 Position
Pumps should be installed in a protected environment – not exposed to weather. Make sure that there are no obstructions to
prevent proper motor cooling.
5.2 Anchoring
The pump must be secured to a solid foundation by bolts through the holes in the flange or base plate.
An illustration of page 9 shows the bolt location and the pipe connections.
5.3 Installation example
When positioning and installing the pump, follow the installation examples next page in order to avoid damaging the
pump.
Pos.
1
Pipe support: Support piping system properly to avoid stresses on connections.
On-off valves: Install on-off valves for easy access- before the pump intake and after
2
the pump discharge.
Use flexible piping on both input and output sides of the pump to reduce vibration and
3
transmission of noise.
Check valves will prevent return flow of pumped liquid when pump is stopped, reducing
4
the danger of pump damage.
Control Panel: Use high quality components. Make sure that the panel conforms to
5
local standards and regulations.
6
Do not place elbows next to the pump intake and discharge.
If pump needs to be operated with on-off valve closed, install a by-pass line to avoid
7
damaging the pumping system.
!!!!!!!!!!!!!!!!!!!!!!!!!!!!!